Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2022 |
Principal Product | Turbine |
NAICS | 333611 - Turbine and Turbine Generator Set Units Manufacturing |
SIC | 3511 - Turbines And Turbine Generator Sets |
Sales | $100,000,000-$500,000,000 |
# of Employees | 350 |
Plant Area (Sq.Ft.) | 150,030 |
Annual Production | 21,018 Pieces |
Production Hrs. Annual | 8,736 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,360,375 | 18,708,884 | kWh | $0.07 |
Electricity Demand | $992,930 | 164,836 | kW-months/year | $6.02 |
Electricity Fees | $124,856 | - | $ | - |
TOTAL ENERGY COSTS | $2,478,161 | |||
RECOMMENDED SAVINGS* | $221,535 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $130,833 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $40,534 Cost: $120 |
$36,456 | 492,650 | $4,078 | 677 |
$36,456 492,650 kWh |
$4,078 677 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD |
Savings: $36,341 Cost: $63,560 |
$32,684 | 441,669 | $3,657 | 607 |
$32,684 441,669 kWh |
$3,657 607 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $35,363 Cost: $35,990 |
$31,809 | 429,852 | $3,554 | 590 |
$31,809 429,852 kWh |
$3,554 590 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $26,496 Cost: $1,980 |
$23,815 | 321,820 | $2,681 | 445 |
$23,815 321,820 kWh |
$2,681 445 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4323 USE OPTIMUM SIZE AND CAPACITY EQUIPMENT |
Savings: $25,810 Cost: $4,691 |
$23,214 | 313,700 | $2,596 | 431 |
$23,214 313,700 kWh |
$2,596 431 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $20,628 Cost: $8,462 |
$18,556 | 250,752 | $2,072 | 344 |
$18,556 250,752 kWh |
$2,072 344 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $11,441 Cost: $2,980 |
$10,290 | 139,053 | $1,151 | 191 |
$10,290 139,053 kWh |
$1,151 191 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $9,012 Cost: $25,709 |
$8,108 | 109,564 | $904 | 150 |
$8,108 109,564 kWh |
$904 150 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $7,987 Cost: $2,137 |
$7,186 | 97,104 | $801 | 133 |
$7,186 97,104 kWh |
$801 133 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $7,621 Cost: $465 |
$6,856 | 92,653 | $765 | 127 |
$6,856 92,653 kWh |
$765 127 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7423 REDUCE HEAT GAIN BY WINDOW TINTING |
Savings: $302 Cost: $1,470 |
$213 | 2,880 | $89 | 15 |
$213 2,880 kWh |
$89 15 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $221,535 Cost: $147,564 |
$199,187 | 2,691,697 | $22,348 | 3,710 | $199,187 2,691,697 kWh |
$22,348 3,710 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $130,833 Cost: $68,916 |
$117,664 | 1,590,043 | $13,169 | 2,186 | $117,664 1,590,043 kWh |
$13,169 2,186 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand |