Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2023 |
Principal Product | Vitamins, Supplements |
NAICS | 325412 - Pharmaceutical Preparation Manufacturing |
SIC | 2834 - Pharmaceutical Preparations |
Sales | $50,000,000-$100,000,000 |
# of Employees | 340 |
Plant Area (Sq.Ft.) | 132,000 |
Annual Production | 12,480,000 Pieces |
Production Hrs. Annual | 4,160 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $103,792 | 1,720,688 | kWh | $0.06 |
Electricity Demand | $69,988 | 4,663 | kW-months/year | $15.01 |
Electricity Fees | $47,499 | - | $ | - |
TOTAL ENERGY COSTS | $221,279 | |||
RECOMMENDED SAVINGS* | $3,202,254 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $3,202,254 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Primary Product | Electricity Usage | Electricity Demand | Primary Product | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7273 INSTALL DESICCANT HUMIDITY CONTROL SYSTEM |
Savings: $3,141,406 Cost: $1,000,000 |
$(-4,992) | (-83,200) | $(-3,602) | (-240) | $3,150,000 | - |
$(-4,992) (-83,200) kWh |
$(-3,602) (-240) kW-months/year |
$3,150,000 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $22,029 Cost: $480 |
$12,798 | 213,308 | $9,231 | 615 | - | - |
$12,798 213,308 kWh |
$9,231 615 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $14,894 Cost: $1,980 |
$8,650 | 144,163 | $6,244 | 416 | - | - |
$8,650 144,163 kWh |
$6,244 416 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS |
Savings: $5,903 Cost: $1,827 |
- | - | $5,903 | 393 | - | - |
- - kWh |
$5,903 393 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $4,785 Cost: $13,440 |
$2,804 | 46,737 | $1,981 | 132 | - | - |
$2,804 46,737 kWh |
$1,981 132 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7229 AIR CONDITION ONLY SPACE NECESSARY |
Savings: $3,663 Cost: $3,360 |
$3,663 | 61,047 | - | - | - | - |
$3,663 61,047 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7442 KEEP DOORS AND WINDOWS SHUT WHEN NOT ON USE |
Savings: $2,508 Cost: - |
$1,457 | 24,279 | $1,051 | 70 | - | - |
$1,457 24,279 kWh |
$1,051 70 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7444 CLOSE HOLES AND OPENINGS IN BUILDING SUCH AS BROKEN WINDOWS |
Savings: $1,021 Cost: $199 |
$760 | 12,660 | $261 | 17 | - | - |
$760 12,660 kWh |
$261 17 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $6,045 Cost: - |
- | - | $6,045 | 403 | - | - |
- - kWh |
$6,045 403 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $3,202,254 Cost: $1,021,286 |
$25,140 | 418,994 | $27,114 | 1,807 | $3,150,000 | - | $25,140 418,994 kWh |
$27,114 1,807 kW-months/year |
$3,150,000 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $3,202,254 Cost: $1,021,286 |
$25,140 | 418,994 | $27,114 | 1,807 | $3,150,000 | - | $25,140 418,994 kWh |
$27,114 1,807 kW-months/year |
$3,150,000 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |