Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Miami
Assessment Year 2024
Principal Product Plastics
NAICS 326199 - All Other Plastics Product Manufacturing
SIC 3089 - Plastics Products, Nec
Sales $5,000,000-$10,000,000
# of Employees 46
Plant Area (Sq.Ft.) 24,600
Annual Production 50,000,000 Pieces
Production Hrs. Annual 4,992
Location (State) PR
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $326,188 1,634,160 kWh $0.20
Electricity Demand $50,435 5,569 kW-months/year $9.06
Electricity Fees $2,761 - $ -
LPG $28 1 MMBtu $28.16
TOTAL ENERGY COSTS $379,411
RECOMMENDED SAVINGS* $70,631 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Fees LPG Electricity Usage Electricity Demand Electricity Fees LPG
$ kWh $ kW-months/year $ $ $ MMBtu
01: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE Savings:
$43,159
Cost:
$3,200
- - - - $43,159 - - - -
-
kWh
-
-
kW-months/year
$43,159
-
$
-
-
MMBtu
02: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$16,369
Cost:
$4,496
$14,766 73,828 $1,603 177 - - - - $14,766
73,828
kWh
$1,603
177
kW-months/year
-
-
$
-
-
MMBtu
03: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$7,120
Cost:
$17,650
- - $7,120 786 - - - - -
-
kWh
$7,120
786
kW-months/year
-
-
$
-
-
MMBtu
04: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT Savings:
$2,036
Cost:
$240
$2,690 13,452 $639 71 - - $(-1,293) (-46) $2,690
13,452
kWh
$639
71
kW-months/year
-
-
$
$(-1,293)
(-46)
MMBtu
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$1,894
Cost:
$80
$1,686 8,429 $208 23 - - - - $1,686
8,429
kWh
$208
23
kW-months/year
-
-
$
-
-
MMBtu
06: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA Savings:
$53
Cost:
-
$48 241 $5 1 - - - - $48
241
kWh
$5
1
kW-months/year
-
-
$
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$70,631
Cost:
$25,666
$19,190 95,950 $9,575 1,057 $43,159 - $(-1,293) (-46) $19,190
95,950
kWh
$9,575
1,057
kW-months/year
$43,159
-
$
$(-1,293)
(-46)
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - - - -
-
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ $ $ MMBtu
Electricity Usage Electricity Demand Electricity Fees LPG Electricity Usage Electricity Demand Electricity Fees LPG