Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Mississippi State |
---|---|
Assessment Year | 2006 |
Principal Product | recycled paper |
NAICS | 322121 - Paper (except Newsprint) Mills |
SIC | 2611 - Pulp Mills |
Sales | $10,000,000-$50,000,000 |
# of Employees | 88 |
Plant Area (Sq.Ft.) | 550,000 |
Annual Production | 96,200 Tons |
Production Hrs. Annual | 7,392 |
Location (State) | MS |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $2,353,170 | 68,207,832 | kWh | $0.03 |
Electricity Demand | $739,507 | 129,284 | kW-months/year | $5.72 |
Electricity Fees | $13,575,693 | - | $ | - |
Natural Gas | $1,546,515 | 222,197 | MMBtu | $6.96 |
TOTAL ENERGY COSTS | $18,214,885 | |||
RECOMMENDED SAVINGS* | $389,750 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $71,515 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $224,456 Cost: $74,722 |
$21,383 | 619,793 | $5,647 | 1,006 | $197,426 | - | - | - |
$21,383 619,793 kWh |
$5,647 1,006 kW-months/year |
$197,426 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $42,324 Cost: $29,520 |
- | - | - | - | - | - | $42,324 | 6,081 |
- - kWh |
- - kW-months/year |
- - $ |
$42,324 6,081 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $38,212 Cost: $8,550 |
$3,590 | 104,052 | $1,387 | 245 | $33,235 | - | - | - |
$3,590 104,052 kWh |
$1,387 245 kW-months/year |
$33,235 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $28,523 Cost: $2,000 |
- | - | - | - | - | - | $28,523 | 4,098 |
- - kWh |
- - kW-months/year |
- - $ |
$28,523 4,098 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $18,397 Cost: $233 |
$1,808 | 52,397 | - | - | $16,589 | - | - | - |
$1,808 52,397 kWh |
- - kW-months/year |
$16,589 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $10,825 Cost: $34,509 |
$1,029 | 29,823 | $292 | 52 | $9,504 | - | - | - |
$1,029 29,823 kWh |
$292 52 kW-months/year |
$9,504 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $10,794 Cost: $1,853 |
- | - | - | - | - | - | $10,794 | 1,551 |
- - kWh |
- - kW-months/year |
- - $ |
$10,794 1,551 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS |
Savings: $9,158 Cost: $169 |
- | - | - | - | - | - | $9,158 | 1,315 |
- - kWh |
- - kW-months/year |
- - $ |
$9,158 1,315 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7229 AIR CONDITION ONLY SPACE NECESSARY |
Savings: $6,088 Cost: $600 |
$428 | 12,312 | $1,454 | 259 | $4,206 | - | - | - |
$428 12,312 kWh |
$1,454 259 kW-months/year |
$4,206 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $973 Cost: - |
$96 | 2,774 | - | - | $877 | - | - | - |
$96 2,774 kWh |
- - kW-months/year |
$877 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $389,750 Cost: $152,156 |
$28,334 | 821,151 | $8,780 | 1,562 | $261,837 | - | $90,799 | 13,045 | $28,334 821,151 kWh |
$8,780 1,562 kW-months/year |
$261,837 - $ |
$90,799 13,045 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $71,515 Cost: $31,606 |
$1,808 | 52,397 | - | - | $16,589 | - | $53,118 | 7,632 | $1,808 52,397 kWh |
- - kW-months/year |
$16,589 - $ |
$53,118 7,632 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas |