Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Mississippi State |
---|---|
Assessment Year | 2008 |
Principal Product | Paper |
NAICS | 322121 - Paper (except Newsprint) Mills |
SIC | 2621 - Paper Mills |
Sales | $10,000,000-$50,000,000 |
# of Employees | 38 |
Plant Area (Sq.Ft.) | 125,000 |
Annual Production | 23,400,000 Pounds |
Production Hrs. Annual | 8,064 |
Location (State) | MS |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $777,024 | 19,087,992 | kWh | $0.04 |
Electricity Demand | $125,226 | 33,898 | kW-months/year | $3.69 |
Electricity Fees | $414,432 | - | $ | - |
Natural Gas | $889,389 | 112,537 | MMBtu | $7.90 |
TOTAL ENERGY COSTS | $2,206,071 | |||
RECOMMENDED SAVINGS* | $72,402 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $41,984 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS |
Savings: $41,488 Cost: $312 |
- | - | - | - | - | - | $41,488 | 5,160 |
- - kWh |
- - kW-months/year |
- - $ |
$41,488 5,160 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $13,055 Cost: $401 |
$13,055 | 319,767 | - | - | - | - | - | - |
$13,055 319,767 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $11,964 Cost: $28,674 |
$10,436 | 259,463 | $1,351 | 386 | $177 | - | - | - |
$10,436 259,463 kWh |
$1,351 386 kW-months/year |
$177 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $2,856 Cost: $600 |
$2,401 | 59,685 | $414 | 118 | $41 | - | - | - |
$2,401 59,685 kWh |
$414 118 kW-months/year |
$41 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED |
Savings: $2,543 Cost: $100 |
$2,219 | 55,158 | $287 | 82 | $37 | - | - | - |
$2,219 55,158 kWh |
$287 82 kW-months/year |
$37 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $289 Cost: $1,324 |
$246 | 6,123 | $39 | 11 | $4 | - | - | - |
$246 6,123 kWh |
$39 11 kW-months/year |
$4 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.6214 SHUT OFF PILOTS IN STANDBY EQUIPMENT |
Savings: $207 Cost: $24 |
- | - | - | - | - | - | $207 | 26 |
- - kWh |
- - kW-months/year |
- - $ |
$207 26 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $72,402 Cost: $31,435 |
$28,357 | 700,196 | $2,091 | 597 | $259 | - | $41,695 | 5,186 | $28,357 700,196 kWh |
$2,091 597 kW-months/year |
$259 - $ |
$41,695 5,186 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $41,984 Cost: $1,660 |
$246 | 6,123 | $39 | 11 | $4 | - | $41,695 | 5,186 | $246 6,123 kWh |
$39 11 kW-months/year |
$4 - $ |
$41,695 5,186 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas |