Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Mississippi State |
---|---|
Assessment Year | 2009 |
Principal Product | LUMBER |
NAICS | 321114 - Wood Preservation |
SIC | 2491 - Wood Preserving |
Sales | $10,000,000-$50,000,000 |
# of Employees | 54 |
Plant Area (Sq.Ft.) | 367,000 |
Annual Production | 260,000 Thousand Feet |
Production Hrs. Annual | 2,205 |
Location (State) | AL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $356,948 | 5,871,600 | kWh | $0.06 |
Electricity Demand | $107,550 | 26,647 | kW-months/year | $4.04 |
Electricity Fees | $39,382 | - | $ | - |
TOTAL ENERGY COSTS | $503,880 | |||
RECOMMENDED SAVINGS* | $50,688 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $23,599 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Wood | Electricity Usage | Electricity Demand | Electricity Fees | Wood | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $18,308 Cost: $7,084 |
$17,984 | 295,835 | - | - | $324 | - | - | - |
$17,984 295,835 kWh |
- - kW-months/year |
$324 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS |
Savings: $13,965 Cost: $187 |
- | - | - | - | - | - | $13,965 | 4,074 |
- - kWh |
- - kW-months/year |
- - $ |
$13,965 4,074 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $5,762 Cost: $10,935 |
$4,150 | 68,272 | $1,510 | 372 | $102 | - | - | - |
$4,150 68,272 kWh |
$1,510 372 kW-months/year |
$102 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $4,977 Cost: $4,445 |
$3,695 | 60,786 | $1,194 | 294 | $88 | - | - | - |
$3,695 60,786 kWh |
$1,194 294 kW-months/year |
$88 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,379 Cost: $462 |
$3,319 | 54,591 | - | - | $60 | - | - | - |
$3,319 54,591 kWh |
- - kW-months/year |
$60 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,924 Cost: $12,190 |
$1,387 | 22,821 | $503 | 124 | $34 | - | - | - |
$1,387 22,821 kWh |
$503 124 kW-months/year |
$34 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $1,095 Cost: $630 |
$1,076 | 17,698 | - | - | $19 | - | - | - |
$1,076 17,698 kWh |
- - kW-months/year |
$19 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $948 Cost: $864 |
$931 | 15,321 | - | - | $17 | - | - | - |
$931 15,321 kWh |
- - kW-months/year |
$17 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $330 Cost: $168 |
- | - | - | - | - | - | $330 | 97 |
- - kWh |
- - kW-months/year |
- - $ |
$330 97 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $50,688 Cost: $36,965 |
$32,542 | 535,324 | $3,207 | 790 | $644 | - | $14,295 | 4,171 | $32,542 535,324 kWh |
$3,207 790 kW-months/year |
$644 - $ |
$14,295 4,171 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $23,599 Cost: $6,126 |
$7,945 | 130,698 | $1,194 | 294 | $165 | - | $14,295 | 4,171 | $7,945 130,698 kWh |
$1,194 294 kW-months/year |
$165 - $ |
$14,295 4,171 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Wood | Electricity Usage | Electricity Demand | Electricity Fees | Wood |