Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Missouri-Columbia |
---|---|
Assessment Year | 2019 |
Principal Product | Farming Equipment |
NAICS | 333111 - Farm Machinery and Equipment Manufacturing |
SIC | 3523 - Farm Machinery And Equipment |
Sales | $50,000,000-$100,000,000 |
# of Employees | 210 |
Plant Area (Sq.Ft.) | 349,000 |
Annual Production | 4,800 Tons |
Production Hrs. Annual | 2,000 |
Location (State) | KS |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $175,405 | 4,088,960 | kWh | $0.04 |
Electricity Demand | $363,652 | 17,222 | kW-months/year | $21.12 |
Electricity Fees | $2,659 | - | $ | - |
Natural Gas | $161,380 | 32,835 | MMBtu | $4.91 |
TOTAL ENERGY COSTS | $703,096 | |||
RECOMMENDED SAVINGS* | $84,676 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $50,282 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.8121 APPLY FOR TAX-FREE STATUS FOR ENERGY PURCHASES |
Savings: $22,096 Cost: $10,000 |
- | - | - | - | $22,096 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$22,096 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $20,740 Cost: $2,302 |
- | - | $20,740 | 982 | - | - | - | - | - | - |
- - kWh |
$20,740 982 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $9,670 Cost: $3,552 |
$2,447 | 57,030 | $7,223 | 342 | - | - | - | - | - | - |
$2,447 57,030 kWh |
$7,223 342 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $5,073 Cost: $1,940 |
$1,926 | 44,894 | $3,147 | 149 | - | - | - | - | - | - |
$1,926 44,894 kWh |
$3,147 149 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $2,922 Cost: $1,406 |
$876 | 20,411 | $2,598 | 123 | - | - | - | - | $(-552) | - |
$876 20,411 kWh |
$2,598 123 kW-months/year |
- - $ |
- - MMBtu |
$(-552) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $3,079 Cost: $2,052 |
$777 | 18,121 | $2,302 | 109 | - | - | - | - | - | - |
$777 18,121 kWh |
$2,302 109 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $3,033 Cost: $4,192 |
$765 | 17,822 | $2,268 | 107 | - | - | - | - | - | - |
$765 17,822 kWh |
$2,268 107 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $14,079 Cost: $20,625 |
- | - | - | - | $14,079 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$14,079 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.2531 RE-SIZE CHARGING OPENINGS OR ADD MOVABLE COVER OR DOOR |
Savings: $3,984 Cost: $2,731 |
$(-54) | (-1,260) | $(-160) | (-8) | - | - | $4,198 | 855 | - | - |
$(-54) (-1,260) kWh |
$(-160) (-8) kW-months/year |
- - $ |
$4,198 855 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $84,676 Cost: $48,800 |
$6,737 | 157,018 | $38,118 | 1,804 | $36,175 | - | $4,198 | 855 | $(-552) | - | $6,737 157,018 kWh |
$38,118 1,804 kW-months/year |
$36,175 - $ |
$4,198 855 MMBtu |
$(-552) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $50,282 Cost: $40,215 |
$4,344 | 101,248 | $10,315 | 488 | $36,175 | - | - | - | $(-552) | - | $4,344 101,248 kWh |
$10,315 488 kW-months/year |
$36,175 - $ |
- - MMBtu |
$(-552) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes |