Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Missouri-Columbia
Assessment Year 2020
Principal Product wood based glass windows
NAICS 332321 - Metal Window and Door Manufacturing
SIC 3442 - Metal Doors, Sash, And Trim
Sales $50,000,000-$100,000,000
# of Employees 454
Plant Area (Sq.Ft.) 341,000
Annual Production 1,250,280 Pieces
Production Hrs. Annual 4,160
Location (State) MO
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $250,031 3,870,720 kWh $0.06
Electricity Demand $35,488 11,301 kW-months/year $3.14
LPG $74,108 10,149 MMBtu $7.30
TOTAL ENERGY COSTS $359,627
RECOMMENDED SAVINGS* $20,401 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $10,909
#|Description Savings
Cost
Status Electricity Usage Electricity Demand LPG One-time Revenue or Avoided Cost Electricity Usage Electricity Demand LPG One-time Revenue or Avoided Cost
$ kWh $ kW-months/year $ MMBtu $ $
01: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$2,251
Cost:
$400
$1,972 30,819 $279 89 - - - - $1,972
30,819
kWh
$279
89
kW-months/year
-
-
MMBtu
-
-
$
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$2,114
Cost:
$4,500
$1,129 17,472 $158 50 - - $827 - $1,129
17,472
kWh
$158
50
kW-months/year
-
-
MMBtu
$827
-
$
03: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$4,820
Cost:
$7,000
$4,225 65,707 $595 190 - - - - $4,225
65,707
kWh
$595
190
kW-months/year
-
-
MMBtu
-
-
$
04: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$3,146
Cost:
$7,360
$1,904 30,845 $1,242 396 - - - - $1,904
30,845
kWh
$1,242
396
kW-months/year
-
-
MMBtu
-
-
$
05: 2.2425 USE FLUE GASES TO HEAT PROCESS OR SERVICE WATER Savings:
$2,963
Cost:
$4,300
- - - - $2,963 406 - - -
-
kWh
-
-
kW-months/year
$2,963
406
MMBtu
-
-
$
06: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$1,087
Cost:
$5,000
$953 14,756 $134 43 - - - - $953
14,756
kWh
$134
43
kW-months/year
-
-
MMBtu
-
-
$
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$604
Cost:
$200
$604 9,351 - - - - - - $604
9,351
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
08: 2.6127 MAINTAIN AIR FILTERS BY CLEANING OR REPLACEMENT Savings:
$304
Cost:
$52
$304 4,702 - - - - - - $304
4,702
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
09: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$673
Cost:
$405
$589 9,209 $84 27 - - - - $589
9,209
kWh
$84
27
kW-months/year
-
-
MMBtu
-
-
$
10: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$1,307
Cost:
$4,100
$1,307 20,110 - - - - - - $1,307
20,110
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
11: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$1,132
Cost:
$1,720
$1,132 17,422 - - - - - - $1,132
17,422
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
TOTAL RECOMMENDED Savings:
$20,401
Cost:
$35,037
$14,119 220,393 $2,492 794 $2,963 406 $827 - $14,119
220,393
kWh
$2,492
794
kW-months/year
$2,963
406
MMBtu
$827
-
$
TOTAL IMPLEMENTED Savings:
$10,909
Cost:
$21,257
$9,111 141,307 $971 309 - - $827 - $9,111
141,307
kWh
$971
309
kW-months/year
-
-
MMBtu
$827
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $
Electricity Usage Electricity Demand LPG One-time Revenue or Avoided Cost Electricity Usage Electricity Demand LPG One-time Revenue or Avoided Cost