Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | North Carolina State |
---|---|
Assessment Year | 1998 |
Principal Product | scissors and medical instruments |
NAICS | n/a |
SIC | 3841 - Surgical And Medical Instruments |
Sales | $50,000,000-$100,000,000 |
# of Employees | 160 |
Plant Area (Sq.Ft.) | 56,975 |
Annual Production | 5,000,000 Pieces |
Production Hrs. Annual | 6,000 |
Location (State) | NC |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $97,148 | 2,572,978 | kWh | $0.04 |
Electricity Demand | $56,032 | 7,722 | kW-months/year | $7.26 |
Electricity Fees | $4,702 | - | $ | - |
TOTAL ENERGY COSTS | $169,382 | |||
RECOMMENDED SAVINGS* | $61,002 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Solid Waste (haz) | Personnel Changes | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Solid Waste (haz) | Personnel Changes | Administrative Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | lb | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,157 Cost: $600 |
$752 | 24,326 | $405 | 49 | - | - | - | - | - | - | - | - |
$752 24,326 kWh |
$405 49 kW-months/year |
- - lb |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $33,411 Cost: $132,700 |
$20,695 | 667,644 | $12,716 | 1,487 | - | - | - | - | - | - | - | - |
$20,695 667,644 kWh |
$12,716 1,487 kW-months/year |
- - lb |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7491 INSULATE GLAZING, WALLS, CEILINGS, AND ROOFS |
Savings: $401 Cost: $1,500 |
$210 | 6,741 | $191 | 21 | - | - | - | - | - | - | - | - |
$210 6,741 kWh |
$191 21 kW-months/year |
- - lb |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2692 USE OUTSIDE COLD WATER SOURCE AS A SUPPLY OF COOLING WATER |
Savings: $700 Cost: $2,100 |
$259 | 8,499 | $441 | 49 | - | - | - | - | - | - | - | - |
$259 8,499 kWh |
$441 49 kW-months/year |
- - lb |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $5,290 Cost: $3,000 |
$2,088 | 72,098 | $1,202 | 144 | - | - | - | - | $2,000 | - | - | - |
$2,088 72,098 kWh |
$1,202 144 kW-months/year |
- - lb |
- - $ |
$2,000 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 3.5146 UTILIZE A CENTRAL COOLANT SYSTEM FOR CLEANING AND REUSE OF METAL WORKING FLUID |
Savings: $3,822 Cost: $15,000 |
- | - | - | - | - | - | - | - | - | - | $3,822 | - |
- - kWh |
- - kW-months/year |
- - lb |
- - $ |
- - $ |
$3,822 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 3.3127 USE ADSORPTION, ION EXCHANGE TO REMOVE CONTAMINANTS |
Savings: $11,500 Cost: $45,000 |
- | - | - | - | $11,500 | 40,000 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$11,500 40,000 lb |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 3.3131 USE EVAPORATION TO CONCENTRATE MATERIAL |
Savings: $4,721 Cost: $16,000 |
$(-620) | (-19,930) | - | - | $6,541 | 22,750 | $(-700) | - | $(-500) | - | - | - |
$(-620) (-19,930) kWh |
- - kW-months/year |
$6,541 22,750 lb |
$(-700) - $ |
$(-500) - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $61,002 Cost: $215,900 |
$23,384 | 759,378 | $14,955 | 1,750 | $18,041 | 62,750 | $(-700) | - | $1,500 | - | $3,822 | - | $23,384 759,378 kWh |
$14,955 1,750 kW-months/year |
$18,041 62,750 lb |
$(-700) - $ |
$1,500 - $ |
$3,822 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - lb |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | lb | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Solid Waste (haz) | Personnel Changes | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Solid Waste (haz) | Personnel Changes | Administrative Changes | Ancillary Material Cost |