IAC logo
IAC Assessment: NC0278
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: NC0278
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center North Carolina State
Assessment Year 2004
Principal Product pre-cast concrete structures
NAICS 238120 - Structural Steel and Precast Concrete Contractors
SIC 3272 - Concrete Products, Nec
Sales $10,000,000-$50,000,000
# of Employees 120
Plant Area (Sq.Ft.) 140,000
Annual Production 264,600,000 Pounds
Production Hrs. Annual 4,000
Location (State) SC
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $114,542 2,588,109 kWh $0.04
Electricity Demand $16,723 4,905 kW-months/year $3.41
Natural Gas $43,487 3,990 MMBtu $10.90
TOTAL ENERGY COSTS $174,752
RECOMMENDED SAVINGS* $8,626 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $693
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR Savings:
$4,343
Cost:
$18,000
$4,343 49,600 - - $4,343
49,600
kWh
-
-
kW-months/year
02: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$458
Cost:
$1,750
$375 8,200 $83 25 $375
8,200
kWh
$83
25
kW-months/year
03: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$47
Cost:
$25
$37 801 $10 3 $37
801
kWh
$10
3
kW-months/year
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$3,132
Cost:
$630
$2,558 55,965 $574 168 $2,558
55,965
kWh
$574
168
kW-months/year
05: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$574
Cost:
$25
$574 15,120 - - $574
15,120
kWh
-
-
kW-months/year
06: 2.7134 USE PHOTOCELL CONTROLS Savings:
$72
Cost:
$130
$60 1,314 $12 4 $60
1,314
kWh
$12
4
kW-months/year
TOTAL RECOMMENDED Savings:
$8,626
Cost:
$20,560
$7,947 131,000 $679 200 $7,947
131,000
kWh
$679
200
kW-months/year
TOTAL IMPLEMENTED Savings:
$693
Cost:
$180
$671 17,235 $22 7 $671
17,235
kWh
$22
7
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand