Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | North Carolina State |
---|---|
Assessment Year | 2005 |
Principal Product | Cartons for the food industry |
NAICS | 322212 - Folding Paperboard Box Manufacturing |
SIC | 2657 - Folding Paperboard Boxes |
Sales | $10,000,000-$50,000,000 |
# of Employees | 124 |
Plant Area (Sq.Ft.) | 156,000 |
Annual Production | 999,999,999 Pieces |
Production Hrs. Annual | 8,400 |
Location (State) | NC |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $226,006 | 8,128,000 | kWh | $0.03 |
Electricity Demand | $141,768 | 14,799 | kW-months/year | $9.58 |
Electricity Fees | $12,059 | - | $ | - |
Natural Gas | $15,780 | 1,566 | MMBtu | $10.08 |
TOTAL ENERGY COSTS | $395,613 | |||
RECOMMENDED SAVINGS* | $51,041 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $31,841 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $9,359 Cost: $20,313 |
$6,307 | 226,800 | $3,052 | 324 | - | - | - | - | - | - |
$6,307 226,800 kWh |
$3,052 324 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $6,017 Cost: $2,450 |
- | - | - | - | $6,017 | 597 | - | - | - | - |
- - kWh |
- - kW-months/year |
$6,017 597 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 4.211 CONSIDER USE / PURCHASE OF BULK MATERIALS WHERE POSSIBLE |
Savings: $15,600 Cost: $1,000 |
- | - | - | - | - | - | - | - | $15,600 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
$15,600 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $13,767 Cost: $6,500 |
$13,767 | 495,024 | - | - | - | - | - | - | - | - |
$13,767 495,024 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 4.212 ADOPT IN-HOUSE MATERIAL GENERATION |
Savings: $3,600 Cost: $4,000 |
- | - | - | - | - | - | $3,600 | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$3,600 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,493 Cost: $2,000 |
$972 | 34,943 | $521 | 55 | - | - | - | - | - | - |
$972 34,943 kWh |
$521 55 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7132 INSTALL TIMERS ON LIGHT SWITCHES IN LITTLE USED AREAS |
Savings: $867 Cost: $750 |
$629 | 22,630 | $238 | 25 | - | - | - | - | - | - |
$629 22,630 kWh |
$238 25 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $338 Cost: $160 |
$111 | 4,004 | $227 | 24 | - | - | - | - | - | - |
$111 4,004 kWh |
$227 24 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $51,041 Cost: $37,173 |
$21,786 | 783,401 | $4,038 | 428 | $6,017 | 597 | $3,600 | - | $15,600 | - | $21,786 783,401 kWh |
$4,038 428 kW-months/year |
$6,017 597 MMBtu |
$3,600 - $ |
$15,600 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $31,841 Cost: $32,173 |
$21,786 | 783,401 | $4,038 | 428 | $6,017 | 597 | - | - | - | - | $21,786 783,401 kWh |
$4,038 428 kW-months/year |
$6,017 597 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Ancillary Material Cost |