IAC logo
IAC Assessment: NC0576
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: NC0576
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center North Carolina State
Assessment Year 2016
Principal Product Non-woven fabric
NAICS 313230 - Nonwoven Fabric Mills
SIC 2297 - Nonwoven Fabrics
Sales $50,000,000-$100,000,000
# of Employees 150
Plant Area (Sq.Ft.) 160,000
Annual Production 32,000,000 Pounds
Production Hrs. Annual 8,760
Location (State) NC
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $3,709,398 67,474,143 kWh $0.05
Electricity Demand $1,034,374 105,185 kW-months/year $9.83
Natural Gas $496,923 89,084 MMBtu $5.58
TOTAL ENERGY COSTS $5,240,695
RECOMMENDED SAVINGS* $384,172 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $125,224
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$16,790
Cost:
$3,000
- - - - $16,790 2,870 -
-
kWh
-
-
kW-months/year
$16,790
2,870
MMBtu
02: 2.2113 REPAIR OR REPLACE STEAM TRAPS Savings:
$108,434
Cost:
$80,000
- - - - $108,434 18,356 -
-
kWh
-
-
kW-months/year
$108,434
18,356
MMBtu
03: 2.3415 USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT Savings:
$198,172
Cost:
$1,100,000
$484,000 8,800,000 $129,756 13,200 $(-415,584) (-71,040) $484,000
8,800,000
kWh
$129,756
13,200
kW-months/year
$(-415,584)
(-71,040)
MMBtu
04: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT Savings:
$60,776
Cost:
$250,000
$79,200 1,440,000 $21,233 2,160 $(-39,657) (-6,779) $79,200
1,440,000
kWh
$21,233
2,160
kW-months/year
$(-39,657)
(-6,779)
MMBtu
TOTAL RECOMMENDED Savings:
$384,172
Cost:
$1,433,000
$563,200 10,240,000 $150,989 15,360 $(-330,017) (-56,593) $563,200
10,240,000
kWh
$150,989
15,360
kW-months/year
$(-330,017)
(-56,593)
MMBtu
TOTAL IMPLEMENTED Savings:
$125,224
Cost:
$83,000
- - - - $125,224 21,226 -
-
kWh
-
-
kW-months/year
$125,224
21,226
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas