IAC logo
IAC Assessment: NT0027
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: NT0027
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of North Texas
Assessment Year 2024
Principal Product Extruded Plastic Tube Products
NAICS 326220 - Rubber and Plastics Hoses and Belting Manufacturing
SIC 3052 - Rubber & Plastics Hose & Belting
Sales $10,000,000-$50,000,000
# of Employees 101
Plant Area (Sq.Ft.) 76,000
Annual Production 4,200 Thousand Feet
Production Hrs. Annual 6,864
Location (State) TX
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $261,358 2,904,883 kWh $0.09
Electricity Demand $78,313 4,695 kW-months/year $16.68
Electricity Fees $9,547 - $ -
Natural Gas $3,453 270 MMBtu $12.79
TOTAL ENERGY COSTS $352,671
RECOMMENDED SAVINGS* $22,000 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$5,267
Cost:
$5,347
$3,978 44,201 $1,289 77 $3,978
44,201
kWh
$1,289
77
kW-months/year
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$4,456
Cost:
$5,609
$3,365 37,393 $1,091 65 $3,365
37,393
kWh
$1,091
65
kW-months/year
03: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA Savings:
$5,335
Cost:
-
$5,335 59,281 - - $5,335
59,281
kWh
-
-
kW-months/year
04: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$2,533
Cost:
$1,946
- - $2,533 152 -
-
kWh
$2,533
152
kW-months/year
05: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD Savings:
$4,408
Cost:
$3,040
$2,128 23,644 $2,280 137 $2,128
23,644
kWh
$2,280
137
kW-months/year
TOTAL RECOMMENDED Savings:
$22,000
Cost:
$15,942
$14,807 164,519 $7,193 431 $14,807
164,519
kWh
$7,193
431
kW-months/year
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - -
-
kWh
-
-
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand