Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Nevada
Assessment Year 1996
Principal Product custom compounded plastic resins
NAICS n/a
SIC 3087 - Custom Compound Purchased Resins
Sales $10,000,000-$50,000,000
# of Employees 50
Plant Area (Sq.Ft.) 60,000
Annual Production 7,000,000 Pounds
Production Hrs. Annual 6,240
Location (State) NV
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $121,521 2,700,762 kWh $0.04
Electricity Demand $61,316 7,795 kW-months/year $7.87
Electricity Fees $5,463 - $ -
Natural Gas $12,488 2,207 MMBtu $5.66
TOTAL ENERGY COSTS $200,893
RECOMMENDED SAVINGS* $13,816 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $1,694
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Fees Natural Gas Solid Waste (non-haz) Electricity Usage Electricity Demand Electricity Fees Natural Gas Solid Waste (non-haz)
$ kWh $ kW-months/year $ $ $ MMBtu $ lb
01: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$1,263
Cost:
$3,525
- - - - $1,263 - - - - - -
-
kWh
-
-
kW-months/year
$1,263
-
$
-
-
MMBtu
-
-
lb
02: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS Savings:
$1,698
Cost:
$4,225
- - - - - - $1,698 341 - - -
-
kWh
-
-
kW-months/year
-
-
$
$1,698
341
MMBtu
-
-
lb
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$7,602
Cost:
$21,840
$4,951 109,906 $2,651 374 - - - - - - $4,951
109,906
kWh
$2,651
374
kW-months/year
-
-
$
-
-
MMBtu
-
-
lb
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$513
Cost:
$260
$513 11,430 - - - - - - - - $513
11,430
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
-
-
lb
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$1,300
Cost:
$600
$1,300 29,015 - - - - - - - - $1,300
29,015
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
-
-
lb
06: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$438
Cost:
$100
$438 9,965 - - - - - - - - $438
9,965
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
-
-
lb
07: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS Savings:
$394
Cost:
$25
$281 7,620 $113 14 - - - - - - $281
7,620
kWh
$113
14
kW-months/year
-
-
$
-
-
MMBtu
-
-
lb
08: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$503
Cost:
$164
$423 9,379 $80 10 - - - - - - $423
9,379
kWh
$80
10
kW-months/year
-
-
$
-
-
MMBtu
-
-
lb
09: 3.5313 INCREASE AMOUNT OF WASTE RECOVERED FOR RESALE Savings:
$105
Cost:
$30
- - - - - - - - $105 6,500 -
-
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
$105
6,500
lb
TOTAL RECOMMENDED Savings:
$13,816
Cost:
$30,769
$7,906 177,315 $2,844 398 $1,263 - $1,698 341 $105 6,500 $7,906
177,315
kWh
$2,844
398
kW-months/year
$1,263
-
$
$1,698
341
MMBtu
$105
6,500
lb
TOTAL IMPLEMENTED Savings:
$1,694
Cost:
$625
$1,581 36,635 $113 14 - - - - - - $1,581
36,635
kWh
$113
14
kW-months/year
-
-
$
-
-
MMBtu
-
-
lb
Savings
Cost
$ kWh $ kW-months/year $ $ $ MMBtu $ lb
Electricity Usage Electricity Demand Electricity Fees Natural Gas Solid Waste (non-haz) Electricity Usage Electricity Demand Electricity Fees Natural Gas Solid Waste (non-haz)