Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Old Dominion Univ. |
---|---|
Assessment Year | 1998 |
Principal Product | Rebuilt Machinery |
NAICS | n/a |
SIC | 3559 - Special Industry Machinery, Nec |
Sales | $50,000,000-$100,000,000 |
# of Employees | 125 |
Plant Area (Sq.Ft.) | 150,000 |
Annual Production | 50 Pieces |
Production Hrs. Annual | 3,640 |
Location (State) | VA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $105,378 | 5,509,086 | kWh | $0.02 |
Electricity Demand | $27,074 | 18,872 | kW-months/year | $1.43 |
Electricity Fees | $218,804 | - | $ | - |
Natural Gas | $5,581 | 1,398 | MMBtu | $3.99 |
TOTAL ENERGY COSTS | $381,678 | |||
RECOMMENDED SAVINGS* | $20,247 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $13,750 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Water Disposal | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Water Disposal | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | Tgal | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $6,497 Cost: $7,621 |
$3,474 | 173,798 | $3,023 | 239 | - | - | - | - |
$3,474 173,798 kWh |
$3,023 239 kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $127 Cost: $608 |
$68 | 3,224 | $59 | 5 | - | - | - | - |
$68 3,224 kWh |
$59 5 kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,198 Cost: $920 |
$1,198 | 62,720 | - | - | - | - | - | - |
$1,198 62,720 kWh |
- - kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $375 Cost: $100 |
$375 | 19,637 | - | - | - | - | - | - |
$375 19,637 kWh |
- - kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 3.4155 METER WASTE WATER |
Savings: $6,227 Cost: $4,595 |
- | - | - | - | $6,227 | 2,545,784 | - | - |
- - kWh |
- - kW-months/year |
$6,227 2,545,784 Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 4.821 PAY BILLS ON TIME TO AVOID LATE FEES |
Savings: $5,823 Cost: - |
- | - | - | - | - | - | $5,823 | - |
- - kWh |
- - kW-months/year |
- - Tgal |
$5,823 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $20,247 Cost: $13,844 |
$5,115 | 259,379 | $3,082 | 244 | $6,227 | 2,545,784 | $5,823 | - | $5,115 259,379 kWh |
$3,082 244 kW-months/year |
$6,227 2,545,784 Tgal |
$5,823 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $13,750 Cost: $6,223 |
$1,641 | 85,581 | $59 | 5 | $6,227 | 2,545,784 | $5,823 | - | $1,641 85,581 kWh |
$59 5 kW-months/year |
$6,227 2,545,784 Tgal |
$5,823 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | Tgal | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Water Disposal | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Water Disposal | One-time Revenue or Avoided Cost |