Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Oklahoma State University |
---|---|
Assessment Year | 1996 |
Principal Product | Refurbished jet engine parts and manufacturing new engines |
NAICS | n/a |
SIC | 3721 - Aircraft |
Sales | $10,000,000-$50,000,000 |
# of Employees | 690 |
Plant Area (Sq.Ft.) | 703,000 |
Annual Production | 800 Pieces |
Production Hrs. Annual | 7,488 |
Location (State) | KS |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $920,195 | 21,164,420 | kWh | $0.04 |
Electricity Demand | $489,693 | 47,031 | kW-months/year | $10.41 |
Natural Gas | $188,893 | 41,582 | MMBtu | $4.54 |
TOTAL ENERGY COSTS | $1,611,391 | |||
RECOMMENDED SAVINGS* | $52,166 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $47,397 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Other Liquid (non-haz) | Electricity Usage | Electricity Demand | Natural Gas | Other Liquid (non-haz) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | gal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $2,692 Cost: $3,200 |
- | - | - | - | $2,692 | 593 | - | - |
- - kWh |
- - kW-months/year |
$2,692 593 MMBtu |
- - gal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,469 Cost: $1,648 |
$1,294 | 12,309 | $175 | 17 | - | - | - | - |
$1,294 12,309 kWh |
$175 17 kW-months/year |
- - MMBtu |
- - gal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $4,649 Cost: $1,399 |
- | - | - | - | $4,649 | 1,024 | - | - |
- - kWh |
- - kW-months/year |
$4,649 1,024 MMBtu |
- - gal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,295 Cost: $4,770 |
$1,657 | 38,101 | $638 | 61 | - | - | - | - |
$1,657 38,101 kWh |
$638 61 kW-months/year |
- - MMBtu |
- - gal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $120 Cost: $366 |
$120 | 2,638 | - | - | - | - | - | - |
$120 2,638 kWh |
- - kW-months/year |
- - MMBtu |
- - gal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $17,199 Cost: $23,287 |
$12,421 | 286,342 | $4,778 | 459 | - | - | - | - |
$12,421 286,342 kWh |
$4,778 459 kW-months/year |
- - MMBtu |
- - gal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,160 Cost: $4,844 |
$1,560 | 36,049 | $600 | 58 | - | - | - | - |
$1,560 36,049 kWh |
$600 58 kW-months/year |
- - MMBtu |
- - gal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 3.8142 DISTILL CONTAMINATED SOLVENTS FOR REUSE |
Savings: $21,582 Cost: $4,500 |
- | - | - | - | - | - | $21,582 | 2,614 |
- - kWh |
- - kW-months/year |
- - MMBtu |
$21,582 2,614 gal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $52,166 Cost: $44,014 |
$17,052 | 375,439 | $6,191 | 595 | $7,341 | 1,617 | $21,582 | 2,614 | $17,052 375,439 kWh |
$6,191 595 kW-months/year |
$7,341 1,617 MMBtu |
$21,582 2,614 gal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $47,397 Cost: $42,249 |
$16,932 | 372,801 | $6,191 | 595 | $2,692 | 593 | $21,582 | 2,614 | $16,932 372,801 kWh |
$6,191 595 kW-months/year |
$2,692 593 MMBtu |
$21,582 2,614 gal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | gal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Other Liquid (non-haz) | Electricity Usage | Electricity Demand | Natural Gas | Other Liquid (non-haz) |