Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Oklahoma State University |
---|---|
Assessment Year | 2013 |
Principal Product | HVAC components |
NAICS | 333415 - Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen |
SIC | 3585 - Refrigeration And Heating Equipment |
Sales | >$500,000,000 |
# of Employees | 1,000 |
Plant Area (Sq.Ft.) | 2,250,000 |
Annual Production | 10,000,000 Units |
Production Hrs. Annual | 8,760 |
Location (State) | KS |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $2,092,559 | 27,468,097 | kWh | $0.08 |
Electricity Demand | $675,658 | 65,218 | kW-months/year | $10.36 |
Natural Gas | $299,258 | 38,608 | MMBtu | $7.75 |
TOTAL ENERGY COSTS | $3,067,475 | |||
RECOMMENDED SAVINGS* | $494,391 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $91,444 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7226 USE COMPUTER PROGRAMS TO OPTIMIZE HVAC PERFORMANCE |
Savings: $21,170 Cost: $53,000 |
$4,461 | 58,693 | - | - | $16,709 | 2,156 | - | - |
$4,461 58,693 kWh |
- - kW-months/year |
$16,709 2,156 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7231 USE RADIANT HEATER FOR SPOT HEATING |
Savings: $52,275 Cost: $107,250 |
- | - | - | - | $52,275 | 6,745 | - | - |
- - kWh |
- - kW-months/year |
$52,275 6,745 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7211 CLEAN AND MAINTAIN REFRIGERANT CONDENSERS AND TOWERS |
Savings: $52,815 Cost: $21,105 |
$36,540 | 480,787 | $16,276 | 1,571 | - | - | - | - |
$36,540 480,787 kWh |
$16,276 1,571 kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7491 INSULATE GLAZING, WALLS, CEILINGS, AND ROOFS |
Savings: $7,057 Cost: $128,411 |
$2,229 | 29,330 | - | - | $4,828 | 623 | - | - |
$2,229 29,330 kWh |
- - kW-months/year |
$4,828 623 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD |
Savings: $242,685 Cost: $1,298,400 |
$204,498 | 2,690,765 | $38,187 | 3,686 | - | - | - | - |
$204,498 2,690,765 kWh |
$38,187 3,686 kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $664 Cost: $5,625 |
$664 | 8,733 | - | - | - | - | - | - |
$664 8,733 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $5,837 Cost: $5,254 |
$5,837 | 60,777 | - | - | - | - | - | - |
$5,837 60,777 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $8,801 Cost: $21,780 |
$8,801 | 115,801 | - | - | - | - | - | - |
$8,801 115,801 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $24,000 Cost: $1,708 |
- | - | - | - | $24,000 | 3,097 | - | - |
- - kWh |
- - kW-months/year |
$24,000 3,097 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $22,770 Cost: $5,000 |
$22,770 | 299,608 | - | - | - | - | - | - |
$22,770 299,608 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $5,138 Cost: $7,536 |
$5,138 | 67,606 | - | - | - | - | - | - |
$5,138 67,606 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $18,213 Cost: $10,212 |
- | - | $18,213 | 1,758 | - | - | - | - |
- - kWh |
$18,213 1,758 kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING |
Savings: $32,965 Cost: $56,937 |
- | - | - | - | - | - | $32,965 | 9,909,000 |
- - kWh |
- - kW-months/year |
- - MMBtu |
$32,965 9,909,000 Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $494,391 Cost: $1,722,218 |
$290,938 | 3,812,100 | $72,676 | 7,015 | $97,812 | 12,621 | $32,965 | 9,909,000 | $290,938 3,812,100 kWh |
$72,676 7,015 kW-months/year |
$97,812 12,621 MMBtu |
$32,965 9,909,000 Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $91,444 Cost: $176,296 |
$70,340 | 925,526 | $16,276 | 1,571 | $4,828 | 623 | - | - | $70,340 925,526 kWh |
$16,276 1,571 kW-months/year |
$4,828 623 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal |