Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Oklahoma State University |
---|---|
Assessment Year | 2015 |
Principal Product | Commercial printing |
NAICS | 323111 - Commercial Printing (except Screen and Books) |
SIC | 2754 - Commercial Printing, Gravure |
Sales | $10,000,000-$50,000,000 |
# of Employees | 46 |
Plant Area (Sq.Ft.) | 65,000 |
Annual Production | 50,000,000 Units |
Production Hrs. Annual | 6,240 |
Location (State) | OK |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $124,169 | 2,194,080 | kWh | $0.06 |
Electricity Demand | $45,311 | 6,364 | kW-months/year | $7.12 |
Natural Gas | $42,048 | 8,504 | MMBtu | $4.94 |
TOTAL ENERGY COSTS | $211,528 | |||
RECOMMENDED SAVINGS* | $68,303 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $11,299 Cost: $3,815 |
$11,299 | 198,235 | - | - | - | - | - | - | - | - |
$11,299 198,235 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7211 CLEAN AND MAINTAIN REFRIGERANT CONDENSERS AND TOWERS |
Savings: $2,194 Cost: - |
$1,939 | 34,024 | $584 | 82 | - | - | - | - | $(-330) | - |
$1,939 34,024 kWh |
$584 82 kW-months/year |
- - $ |
- - MMBtu |
$(-330) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.6232 INSTALL SET-BACK TIMERS |
Savings: $2,270 Cost: $1,550 |
$1,227 | 21,534 | - | - | - | - | $1,042 | 212 | - | - |
$1,227 21,534 kWh |
- - kW-months/year |
- - $ |
$1,042 212 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7496 INSTALL PARTITIONS TO REDUCE SIZE OF CONDITIONED SPACE |
Savings: $820 Cost: $3,450 |
$820 | 14,381 | - | - | - | - | - | - | - | - |
$820 14,381 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,796 Cost: $15,971 |
$3,113 | 54,610 | $684 | 96 | - | - | - | - | - | - |
$3,113 54,610 kWh |
$684 96 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,190 Cost: $5,218 |
$840 | 14,732 | $350 | 49 | - | - | - | - | - | - |
$840 14,732 kWh |
$350 49 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,921 Cost: $2,360 |
$2,605 | 45,702 | $316 | 44 | - | - | - | - | - | - |
$2,605 45,702 kWh |
$316 44 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7211 CLEAN AND MAINTAIN REFRIGERANT CONDENSERS AND TOWERS |
Savings: $1,051 Cost: - |
$2,131 | 37,389 | - | - | - | - | - | - | $(-1,080) | - |
$2,131 37,389 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
$(-1,080) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING |
Savings: $15,138 Cost: $18,243 |
$14,969 | 262,609 | $170 | 24 | - | - | - | - | - | - |
$14,969 262,609 kWh |
$170 24 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,980 Cost: $1,500 |
$3,980 | 69,825 | - | - | - | - | - | - | - | - |
$3,980 69,825 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $3,157 Cost: $20,000 |
- | - | - | - | $3,157 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$3,157 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE |
Savings: $20,000 Cost: $65,000 |
- | - | - | - | $20,000 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$20,000 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $487 Cost: $476 |
$487 | 8,551 | - | - | - | - | - | - | - | - |
$487 8,551 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $68,303 Cost: $137,583 |
$43,410 | 761,592 | $2,104 | 295 | $23,157 | - | $1,042 | 212 | $(-1,410) | - | $43,410 761,592 kWh |
$2,104 295 kW-months/year |
$23,157 - $ |
$1,042 212 MMBtu |
$(-1,410) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Administrative Changes |