Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Oklahoma State University |
---|---|
Assessment Year | 2016 |
Principal Product | Unlaminated plastics profile shape manufacturing |
NAICS | 326121 - Unlaminated Plastics Profile Shape Manufacturing |
SIC | 3089 - Plastics Products, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 320 |
Plant Area (Sq.Ft.) | 450,000 |
Annual Production | 43,000,000 Pounds |
Production Hrs. Annual | 8,088 |
Location (State) | AR |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,352,389 | 33,717,000 | kWh | $0.04 |
Electricity Demand | $1,005,607 | 60,665 | kW-months/year | $16.58 |
Natural Gas | $30,956 | 3,706 | MMBtu | $8.35 |
TOTAL ENERGY COSTS | $2,388,952 | |||
RECOMMENDED SAVINGS* | $253,412 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $197,283 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Electricity Usage | Electricity Demand | Electricity Fees | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING |
Savings: $27,456 Cost: $25,000 |
$27,456 | 684,528 | - | - | - | - |
$27,456 684,528 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $8,615 Cost: $915 |
$8,615 | 214,781 | - | - | - | - |
$8,615 214,781 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2525 ELIMINATE COOLING OF PROCESS STREAMS WHICH SUBSEQUENTLY MUST BE HEATED AND VICE VERSA |
Savings: $134,039 Cost: $1,300 |
$85,245 | 2,125,279 | $48,794 | 2,944 | - | - |
$85,245 2,125,279 kWh |
$48,794 2,944 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $63,243 Cost: $3,161 |
$40,706 | 958,238 | $22,537 | 1,327 | - | - |
$40,706 958,238 kWh |
$22,537 1,327 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $11,990 Cost: - |
- | - | - | - | $11,990 | - |
- - kWh |
- - kW-months/year |
$11,990 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $8,069 Cost: $10,000 |
- | - | - | - | $8,069 | - |
- - kWh |
- - kW-months/year |
$8,069 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $253,412 Cost: $40,376 |
$162,022 | 3,982,826 | $71,332 | 4,271 | $20,059 | - | $162,022 3,982,826 kWh |
$71,332 4,271 kW-months/year |
$20,059 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $197,283 Cost: $4,461 |
$125,951 | 3,083,517 | $71,332 | 4,271 | - | - | $125,951 3,083,517 kWh |
$71,332 4,271 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Electricity Usage | Electricity Demand | Electricity Fees |