IAC logo
IAC Assessment: OK0981
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: OK0981
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Oklahoma State University
Assessment Year 2018
Principal Product Glass containers
NAICS 327213 - Glass Container Manufacturing
SIC 3221 - Glass Containers
Sales $10,000,000-$50,000,000
# of Employees 250
Plant Area (Sq.Ft.) 520,000
Annual Production 730,000,000 Units
Production Hrs. Annual 8,760
Location (State) OK
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $2,485,950 71,371,200 kWh $0.03
Electricity Demand $594,657 108,337 kW-months/year $5.49
Natural Gas $2,717,617 879,684 MMBtu $3.09
TOTAL ENERGY COSTS $5,798,224
RECOMMENDED SAVINGS* $534,717 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $124,716
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Fees Electricity Usage Electricity Demand Electricity Fees
$ kWh $ kW-months/year $ $
01: 2.4224 UPGRADE CONTROLS ON COMPRESSORS Savings:
$124,716
Cost:
$75,000
$102,657 2,933,069 $22,058 4,018 - - $102,657
2,933,069
kWh
$22,058
4,018
kW-months/year
-
-
$
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$7,815
Cost:
-
$6,433 183,796 $1,382 252 - - $6,433
183,796
kWh
$1,382
252
kW-months/year
-
-
$
03: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$16,309
Cost:
$4,937
$16,309 465,964 - - - - $16,309
465,964
kWh
-
-
kW-months/year
-
-
$
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$21,343
Cost:
$69,050
$17,568 501,948 $3,775 688 - - $17,568
501,948
kWh
$3,775
688
kW-months/year
-
-
$
05: 2.2421 INSTALL WASTE HEAT BOILER TO PROVIDE DIRECT POWER Savings:
$353,111
Cost:
$2,500,000
$290,657 8,304,480 $62,454 11,376 - - $290,657
8,304,480
kWh
$62,454
11,376
kW-months/year
-
-
$
06: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$11,423
Cost:
$50,570
- - - - $11,423 - -
-
kWh
-
-
kW-months/year
$11,423
-
$
TOTAL RECOMMENDED Savings:
$534,717
Cost:
$2,699,557
$433,624 12,389,257 $89,670 16,334 $11,423 - $433,624
12,389,257
kWh
$89,670
16,334
kW-months/year
$11,423
-
$
TOTAL IMPLEMENTED Savings:
$124,716
Cost:
$75,000
$102,657 2,933,069 $22,058 4,018 - - $102,657
2,933,069
kWh
$22,058
4,018
kW-months/year
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ $
Electricity Usage Electricity Demand Electricity Fees Electricity Usage Electricity Demand Electricity Fees