IAC logo
IAC Assessment: OK1062
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: OK1062
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Oklahoma State University
Assessment Year 2022
Principal Product heat exchangers
NAICS 332410 - Power Boiler and Heat Exchanger Manufacturing
SIC 3443 - Fabricated Plate Work (boiler Shops)
Sales $10,000,000-$50,000,000
# of Employees 150
Plant Area (Sq.Ft.) 70,000
Annual Production 3,000 Units
Production Hrs. Annual 2,340
Location (State) OK
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $45,311 647,300 kWh $0.07
Electricity Demand $27,880 3,319 kW-months/year $8.40
Natural Gas $32,695 12,117 MMBtu $2.70
TOTAL ENERGY COSTS $105,886
RECOMMENDED SAVINGS* $29,836 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $16,906
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$3,294
Cost:
$2,732
$3,294 47,056 - - - - $3,294
47,056
kWh
-
-
kW-months/year
-
-
MMBtu
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$2,554
Cost:
-
$2,554 36,484 - - - - $2,554
36,484
kWh
-
-
kW-months/year
-
-
MMBtu
03: 2.7231 USE RADIANT HEATER FOR SPOT HEATING Savings:
$12,930
Cost:
$48,590
- - - - $12,930 4,789 -
-
kWh
-
-
kW-months/year
$12,930
4,789
MMBtu
04: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$101
Cost:
$580
$40 568 $61 7 - - $40
568
kWh
$61
7
kW-months/year
-
-
MMBtu
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$10,957
Cost:
$30,186
$6,784 96,918 $4,173 497 - - $6,784
96,918
kWh
$4,173
497
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$29,836
Cost:
$82,088
$12,672 181,026 $4,234 504 $12,930 4,789 $12,672
181,026
kWh
$4,234
504
kW-months/year
$12,930
4,789
MMBtu
TOTAL IMPLEMENTED Savings:
$16,906
Cost:
$33,498
$12,672 181,026 $4,234 504 - - $12,672
181,026
kWh
$4,234
504
kW-months/year
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas