Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Oregon State University |
---|---|
Assessment Year | 2023 |
Principal Product | Support services |
NAICS | 922110 - Courts |
SIC | 8111 - Legal Services |
Sales | <$500,000 |
# of Employees | 400 |
Plant Area (Sq.Ft.) | 98,000 |
Annual Production | 100 Pieces |
Production Hrs. Annual | 3,120 |
Location (State) | OR |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $46,747 | 797,000 | kWh | $0.06 |
Electricity Demand | $24,025 | 3,585 | kW-months/year | $6.70 |
Electricity Fees | $14,677 | - | $ | - |
Natural Gas | $15,898 | 1,496 | MMBtu | $10.63 |
TOTAL ENERGY COSTS | $101,347 | |||
RECOMMENDED SAVINGS* | $17,224 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $6,586 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $765 Cost: $5,150 |
$765 | 12,750 | - | - | - | - |
$765 12,750 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $5,853 Cost: $26,400 |
$5,644 | 96,830 | $209 | 29 | - | - |
$5,644 96,830 kWh |
$209 29 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7314 REDUCE VENTILATION AIR |
Savings: $3,082 Cost: $200 |
$802 | 13,666 | - | - | $2,280 | 215 |
$802 13,666 kWh |
- - kW-months/year |
$2,280 215 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7226 USE COMPUTER PROGRAMS TO OPTIMIZE HVAC PERFORMANCE |
Savings: $808 Cost: $50 |
- | - | - | - | $808 | 76 |
- - kWh |
- - kW-months/year |
$808 76 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7242 CHANGE ZONE REHEAT COILS TO VARIABLE AIR VOLUME BOXES |
Savings: $2,696 Cost: $200 |
$2,696 | 45,970 | - | - | - | - |
$2,696 45,970 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7234 USE HEAT PUMP FOR SPACE CONDITIONING |
Savings: $535 Cost: $5,000 |
$414 | 7,060 | $121 | 18 | - | - |
$414 7,060 kWh |
$121 18 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.1224 REPLACE BOILER |
Savings: $3,485 Cost: $30,000 |
- | - | - | - | $3,485 | 328 |
- - kWh |
- - kW-months/year |
$3,485 328 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $17,224 Cost: $67,000 |
$10,321 | 176,276 | $330 | 47 | $6,573 | 619 | $10,321 176,276 kWh |
$330 47 kW-months/year |
$6,573 619 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $6,586 Cost: $450 |
$3,498 | 59,636 | - | - | $3,088 | 291 | $3,498 59,636 kWh |
- - kW-months/year |
$3,088 291 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |