IAC Center San Diego State University
Assessment Year 2019
Principal Product Water Pipes
NAICS 331210 - Iron and Steel Pipe and Tube Manufacturing from Purchased Steel
SIC 3317 - Steel Pipe And Tubes
Sales $50,000,000
# of Employees 114
Plant Area (Sq.Ft.) 4,200,000
Annual Production 15,000 Tons
Production Hrs. Annual 4,760
Location (State) CA
Source Yearly Cost Usage
Electricity Usage $266,628 3,145,485
Electricity Demand $192,157 12,694
Electricity Fees $17,186 -
TOTAL ENERGY COSTS $475,971
RECOMMENDED SAVINGS* $52,471 *Non-energy impacts
included in savings.
IMPLEMENTED SAVINGS* -
#|Description Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW/month
01: 2.4141 USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS Savings:
$28,925
Cost:
$62,407
$19,282 227,384 $9,643 637 $19,282
227,384
kWh
$9,643
637
kW/month
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$9,727
Cost:
-
$9,727 114,704 - - $9,727
114,704
kWh
-
-
kW/month
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$11,229
Cost:
$21,116
$7,744 91,319 $3,485 230 $7,744
91,319
kWh
$3,485
230
kW/month
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$1,737
Cost:
$1,300
$1,561 18,411 $176 12 $1,561
18,411
kWh
$176
12
kW/month
05: 2.7134 USE PHOTOCELL CONTROLS Savings:
$853
Cost:
$1,600
$853 10,064 - - $853
10,064
kWh
-
-
kW/month
TOTAL RECOMMENDED Savings:
$52,471
Cost:
$86,423
$39,167 461,882 $13,304 879 $39,167
461,882
kWh
$13,304
879
kW/month
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - -
-
kWh
-
-
kW/month
$ kWh $ kW/month
Electricity Usage Electricity Demand Electricity Usage Electricity Demand
Back to Top