IAC logo
IAC Assessment: SD0671
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: SD0671
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Diego State University
Assessment Year 2025
Principal Product Packaging
NAICS 423910 - Sporting and Recreational Goods and Supplies Merchant Wholesalers
SIC 4225 - General Warehousing And Storage
Sales >$500,000,000
# of Employees 65
Plant Area (Sq.Ft.) 289,407
Annual Production 277,862 Units
Production Hrs. Annual 3,125
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $82,457 327,932 kWh $0.25
Electricity Demand $24,334 1,416 kW-months/year $17.19
Electricity Fees $2,741 - $ -
LPG $15,691 178 MMBtu $88.24
TOTAL ENERGY COSTS $125,223
RECOMMENDED SAVINGS* $101,682 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand LPG Electricity Usage Electricity Demand LPG
$ kWh $ kW-months/year $ MMBtu
01: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$72,797
Cost:
$103,994
$56,716 225,602 $16,080 936 - - $56,716
225,602
kWh
$16,080
936
kW-months/year
-
-
MMBtu
02: 2.3141 USE BATTERY STORAGE FOR DEMAND CONTROL Savings:
$2,541
Cost:
$1,352
$(-2,551) (-10,147) $5,092 296 - - $(-2,551)
(-10,147)
kWh
$5,092
296
kW-months/year
-
-
MMBtu
03: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS Savings:
$3,996
Cost:
-
- - $3,996 233 - - -
-
kWh
$3,996
233
kW-months/year
-
-
MMBtu
04: 2.1321 REPLACE FOSSIL FUEL EQUIPMENT WITH ELECTRICAL EQUIPMENT Savings:
$14,911
Cost:
$23,188
$(-780) (-3,103) - - $15,691 178 $(-780)
(-3,103)
kWh
-
-
kW-months/year
$15,691
178
MMBtu
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$6,033
Cost:
$9,226
$5,333 21,214 $700 41 - - $5,333
21,214
kWh
$700
41
kW-months/year
-
-
MMBtu
06: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS Savings:
$1,404
Cost:
-
$1,298 5,163 $107 6 - - $1,298
5,163
kWh
$107
6
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$101,682
Cost:
$137,760
$60,017 238,730 $25,974 1,512 $15,691 178 $60,017
238,730
kWh
$25,974
1,512
kW-months/year
$15,691
178
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand LPG Electricity Usage Electricity Demand LPG