Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Diego State University
Assessment Year 2025
Principal Product Lateral Flow, OTC & POC Test Kits
NAICS 325413 - In-Vitro Diagnostic Substance Manufacturing
SIC 3841 - Surgical And Medical Instruments
Sales $50,000,000-$100,000,000
# of Employees 25
Plant Area (Sq.Ft.) 27,000
Annual Production 221,618 Pieces
Production Hrs. Annual 4,950
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $75,599 221,166 kWh $0.34
Electricity Demand $44,409 826 kW-months/year $53.74
TOTAL ENERGY COSTS $120,008
RECOMMENDED SAVINGS* $91,131 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$43,986
Cost:
$59,050
$43,986 128,690 - - $43,986
128,690
kWh
-
-
kW-months/year
02: 2.3141 USE BATTERY STORAGE FOR DEMAND CONTROL Savings:
$22,813
Cost:
$1,191
$(-2,017) (-5,901) $24,830 462 $(-2,017)
(-5,901)
kWh
$24,830
462
kW-months/year
03: 2.7233 USE PROPERLY DESIGNED AND SIZED HVAC EQUIPMENT Savings:
$10,792
Cost:
$133,100
$10,792 31,573 - - $10,792
31,573
kWh
-
-
kW-months/year
04: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$1,402
Cost:
$4,350
$1,153 3,373 $249 5 $1,153
3,373
kWh
$249
5
kW-months/year
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$2,718
Cost:
-
$2,718 7,953 - - $2,718
7,953
kWh
-
-
kW-months/year
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$3,337
Cost:
$2,362
$2,060 6,027 $1,277 24 $2,060
6,027
kWh
$1,277
24
kW-months/year
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$2,175
Cost:
$5,179
$2,175 6,363 - - $2,175
6,363
kWh
-
-
kW-months/year
08: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$3,908
Cost:
$11,010
$684 2,000 $3,224 60 $684
2,000
kWh
$3,224
60
kW-months/year
TOTAL RECOMMENDED Savings:
$91,131
Cost:
$216,242
$61,551 180,078 $29,580 550 $61,551
180,078
kWh
$29,580
550
kW-months/year
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - -
-
kWh
-
-
kW-months/year
Savings
Cost
$ kWh $ kW-months/year