Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Francisco State University |
---|---|
Assessment Year | 2003 |
Principal Product | Wines |
NAICS | 312130 - Wineries |
SIC | 2084 - Wines, Brandy, And Brandy Spirits |
Sales | $50,000,000-$100,000,000 |
# of Employees | 100 |
Plant Area (Sq.Ft.) | 187,308 |
Annual Production | 0 Units |
Production Hrs. Annual | 2,600 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $540,645 | 4,886,517 | kWh | $0.11 |
Electricity Demand | $151,557 | 12,969 | kW-months/year | $11.69 |
Natural Gas | $50,647 | 8,555 | MMBtu | $5.92 |
TOTAL ENERGY COSTS | $805,255 | |||
RECOMMENDED SAVINGS* | $220,789 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $68,639 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Ancillary Material Cost | Water Consumption | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Ancillary Material Cost | Water Consumption | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $34,947 Cost: $18,680 |
$24,097 | 214,530 | $10,850 | 851 | - | - | - | - | - | - | - | - |
$24,097 214,530 kWh |
$10,850 851 kW-months/year |
- - $ |
- - $ |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $1,323 Cost: $960 |
$519 | 4,661 | $804 | 61 | - | - | - | - | - | - | - | - |
$519 4,661 kWh |
$804 61 kW-months/year |
- - $ |
- - $ |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $768 Cost: $609 |
$646 | 5,806 | $122 | 10 | - | - | - | - | - | - | - | - |
$646 5,806 kWh |
$122 10 kW-months/year |
- - $ |
- - $ |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $14,123 Cost: $17,490 |
$12,148 | 109,244 | $1,975 | 150 | - | - | - | - | - | - | - | - |
$12,148 109,244 kWh |
$1,975 150 kW-months/year |
- - $ |
- - $ |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $3,098 Cost: $7,305 |
$2,818 | 20,541 | $280 | 64 | - | - | - | - | - | - | - | - |
$2,818 20,541 kWh |
$280 64 kW-months/year |
- - $ |
- - $ |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,307 Cost: $3,200 |
$1,113 | 8,113 | $194 | 44 | - | - | - | - | - | - | - | - |
$1,113 8,113 kWh |
$194 44 kW-months/year |
- - $ |
- - $ |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $4,167 Cost: $16,382 |
$3,362 | 30,233 | $805 | 61 | - | - | - | - | - | - | - | - |
$3,362 30,233 kWh |
$805 61 kW-months/year |
- - $ |
- - $ |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $419 Cost: $2,640 |
$419 | 3,772 | - | - | - | - | - | - | - | - | - | - |
$419 3,772 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $13,660 Cost: - |
$(-214) | (-1,920) | $(-106) | (-8) | $(-102) | - | - | - | $14,082 | - | - | - |
$(-214) (-1,920) kWh |
$(-106) (-8) kW-months/year |
$(-102) - $ |
- - $ |
$14,082 - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 3.2172 USE AUTOMATIC CLEANING EQUIPMENT |
Savings: $2,169 Cost: $5,391 |
- | - | - | - | - | - | - | - | - | - | $2,169 | - |
- - kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
$2,169 - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 3.1161 ELIMINATE/REDUCE AN OPERATION |
Savings: $3,120 Cost: $2,865 |
- | - | - | - | $3,120 | - | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$3,120 - $ |
- - $ |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $1,997 Cost: $2,695 |
- | - | $1,997 | - | - | - | - | - | - | - | - | - |
- - kWh |
$1,997 - kW-months/year |
- - $ |
- - $ |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE |
Savings: $90,568 Cost: $162,300 |
- | - | - | - | - | - | $90,568 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$90,568 - $ |
- - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
14: 4.212 ADOPT IN-HOUSE MATERIAL GENERATION |
Savings: $49,123 Cost: $105,624 |
$(-19,938) | (-179,297) | $(-3,241) | (-246) | - | - | - | - | $72,302 | - | - | - |
$(-19,938) (-179,297) kWh |
$(-3,241) (-246) kW-months/year |
- - $ |
- - $ |
$72,302 - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $220,789 Cost: $346,141 |
$24,970 | 215,683 | $13,680 | 987 | $3,018 | - | $90,568 | - | $86,384 | - | $2,169 | - | $24,970 215,683 kWh |
$13,680 987 kW-months/year |
$3,018 - $ |
$90,568 - $ |
$86,384 - $ |
$2,169 - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $68,639 Cost: $56,152 |
$40,331 | 360,520 | $14,328 | 1,115 | $(-102) | - | - | - | $14,082 | - | - | - | $40,331 360,520 kWh |
$14,328 1,115 kW-months/year |
$(-102) - $ |
- - $ |
$14,082 - $ |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Ancillary Material Cost | Water Consumption | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Ancillary Material Cost | Water Consumption |