Select a Center

Arizona State University
Boise State University
Case Western Reserve University
Clemson University
Colorado State University
Georgia Institute of Technology
Indiana University-Purdue University
Lehigh University
Louisiana State University
North Carolina State
Oklahoma State University
Oregon State University
San Diego State University
San Francisco State University
Syracuse University
Tennessee Technological University
Texas A&M, College Station
University of Alabama
University of Dayton
University of Delaware
University of Florida
University of Illinois, Chicago
University of Kentucky
University of Massachusetts
University of Miami
University of Missouri-Columbia
University of Nebraska–Lincoln
University of Texas Rio Grande Valley
University of Utah
University of Wisconsin, Milwaukee
West Virginia University
IAC logo
IAC Assessment: SF0324
Sponsored by:
EERE AMO
IAC logo
IAC Assessment: SF0324
Due to University and State restrictions, IAC assessment activities at your local center may be on hold.
Contact your local center for more details on operating status and available services.

Click here for details about Coronavirus (COVID-19) Recovery Support programs
IAC Center San Francisco State University
Assessment Year 2006
Principal Product Circuit Boards
NAICS 334418 - Printed Circuit Assembly (Electronic Assembly) Manufacturing
SIC 3679 - Electronic Components, Nec
Sales $8,000,000
# of Employees 450
Plant Area (Sq.Ft.) 121,764
Annual Production 130,000 Units
Production Hrs. Annual 4,160
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $453,113 2,277,273 kWh $0.20
Electricity Demand $144,280 8,320 kW-months/year $17.34
Natural Gas $30,748 2,994 MMBtu $10.27
TOTAL ENERGY COSTS $628,141
RECOMMENDED SAVINGS* $131,978 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS Savings:
$11,682
Cost:
$932
$11,682 85,083 - - $11,682
85,083
kWh
-
-
kW-months/year
02: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED Savings:
$5,463
Cost:
-
$5,463 39,789 - - $5,463
39,789
kWh
-
-
kW-months/year
03: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED Savings:
$4,114
Cost:
$240
$4,114 29,970 - - $4,114
29,970
kWh
-
-
kW-months/year
04: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT Savings:
$38,069
Cost:
$4,600
$38,069 277,270 - - $38,069
277,270
kWh
-
-
kW-months/year
05: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$11,113
Cost:
$2,000
$7,983 58,188 $3,130 224 $7,983
58,188
kWh
$3,130
224
kW-months/year
06: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE Savings:
$45,698
Cost:
$37,000
$45,698 - - - $45,698
-
kWh
-
-
kW-months/year
07: 2.7442 KEEP DOORS AND WINDOWS SHUT WHEN NOT ON USE Savings:
$9,724
Cost:
$20,020
$7,598 55,344 $2,126 152 $7,598
55,344
kWh
$2,126
152
kW-months/year
08: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES Savings:
$6,115
Cost:
$24,600
$5,054 44,169 $1,061 52 $5,054
44,169
kWh
$1,061
52
kW-months/year
TOTAL RECOMMENDED Savings:
$131,978
Cost:
$89,392
$125,661 589,813 $6,317 428 $125,661
589,813
kWh
$6,317
428
kW-months/year
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - -
-
kWh
-
-
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand