Select a Center

Arizona State University
Boise State University
Case Western Reserve University
Clemson University
Colorado State University
Georgia Institute of Technology
Indiana University-Purdue University
Lehigh University
Louisiana State University
North Carolina State
Oklahoma State University
Oregon State University
San Diego State University
San Francisco State University
Syracuse University
Tennessee Technological University
Texas A&M, College Station
University of Alabama
University of Dayton
University of Delaware
University of Florida
University of Illinois, Chicago
University of Kentucky
University of Massachusetts
University of Miami
University of Missouri-Columbia
University of Nebraska–Lincoln
University of Texas Rio Grande Valley
University of Utah
University of Wisconsin, Milwaukee
West Virginia University
IAC logo
IAC Assessment: SF0393
Sponsored by:
EERE AMO
IAC logo
IAC Assessment: SF0393
Due to University and State restrictions around the country, all IAC assessment activities are temporarily on hold.
Click here for details about Coronavirus (COVID-19) Recovery Support programs
IAC Center San Francisco State University
Assessment Year 2011
Principal Product Liquid Milk
NAICS 311511 - Fluid Milk Manufacturing
SIC 2026 - Fluid Milk
Sales $10,000,000
# of Employees 385
Plant Area (Sq.Ft.) 41,000
Annual Production 22,000 Thousand Gallons
Production Hrs. Annual 8,112
Location (State) HI
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $1,035,721 5,895,486 kWh $0.18
Electricity Demand $166,405 12,373 kW/month $13.45
Electricity Fees $26,736 - $ -
Natural Gas $314,339 13,907 MMBtu $22.60
TOTAL ENERGY COSTS $1,543,201
RECOMMENDED SAVINGS* $328,667 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $163,858
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW/month $ MMBtu
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$7,408
Cost:
$720
$7,408 42,164 - - - - $7,408
42,164
kWh
-
-
kW/month
-
-
MMBtu
02: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$99,396
Cost:
$33,822
- - - - $99,396 4,398 -
-
kWh
-
-
kW/month
$99,396
4,398
MMBtu
03: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$6,385
Cost:
$4,330
$6,385 36,343 - - - - $6,385
36,343
kWh
-
-
kW/month
-
-
MMBtu
04: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS Savings:
$1,791
Cost:
$1,329
$1,791 10,195 - - - - $1,791
10,195
kWh
-
-
kW/month
-
-
MMBtu
05: 2.2622 REPLACE EXISTING CHILLER WITH HIGH EFFICIENCY MODEL Savings:
$153,800
Cost:
$220,659
$132,585 756,163 $21,215 1,560 - - $132,585
756,163
kWh
$21,215
1,560
kW/month
-
-
MMBtu
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$9,218
Cost:
$19,157
$9,218 52,467 - - - - $9,218
52,467
kWh
-
-
kW/month
-
-
MMBtu
07: 2.1221 REPLACE OBSOLETE BURNERS WITH MORE EFFICIENT ONES Savings:
$32,171
Cost:
$34,310
- - - - $32,171 1,423 -
-
kWh
-
-
kW/month
$32,171
1,423
MMBtu
08: 2.2511 INSULATE BARE EQUIPMENT Savings:
$6,132
Cost:
$17,178
- - - - $6,132 271 -
-
kWh
-
-
kW/month
$6,132
271
MMBtu
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$9,350
Cost:
$25,921
$9,350 37,450 - - - - $9,350
37,450
kWh
-
-
kW/month
-
-
MMBtu
10: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$3,016
Cost:
$14,478
$3,016 13,890 - - - - $3,016
13,890
kWh
-
-
kW/month
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$328,667
Cost:
$371,904
$169,753 948,672 $21,215 1,560 $137,699 6,092 $169,753
948,672
kWh
$21,215
1,560
kW/month
$137,699
6,092
MMBtu
TOTAL IMPLEMENTED Savings:
$163,858
Cost:
$130,759
$26,159 129,847 - - $137,699 6,092 $26,159
129,847
kWh
-
-
kW/month
$137,699
6,092
MMBtu
Savings
Cost
$ kWh $ kW/month $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas