Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Francisco State University |
---|---|
Assessment Year | 2012 |
Principal Product | Canned Tomatoes |
NAICS | 311421 - Fruit and Vegetable Canning |
SIC | 2033 - Canned Fruits And Vegetables |
Sales | $100,000,000-$500,000,000 |
# of Employees | 650 |
Plant Area (Sq.Ft.) | 3,354,120 |
Annual Production | 350,000,000 Pounds |
Production Hrs. Annual | 8,760 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,521,149 | 17,595,933 | kWh | $0.09 |
Electricity Demand | $589,282 | 39,077 | kW-months/year | $15.08 |
Electricity Fees | $24,466 | - | $ | - |
Natural Gas | $2,961,587 | 785,423 | MMBtu | $3.77 |
TOTAL ENERGY COSTS | $5,096,484 | |||
RECOMMENDED SAVINGS* | $221,282 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $83,604 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Personnel Changes | Primary Raw Material | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Personnel Changes | Primary Raw Material | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2153 CLOSE OFF UNNEEDED STEAM LINES |
Savings: $417 Cost: - |
- | - | - | - | $417 | 111 | - | - | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$417 111 MMBtu |
- - Tgal |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS |
Savings: $4,512 Cost: - |
- | - | - | - | $4,512 | 1,197 | - | - | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$4,512 1,197 MMBtu |
- - Tgal |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.6232 INSTALL SET-BACK TIMERS |
Savings: $3,656 Cost: - |
$2,063 | 23,878 | - | - | $1,593 | 423 | - | - | - | - | - | - | - | - |
$2,063 23,878 kWh |
- - kW-months/year |
$1,593 423 MMBtu |
- - Tgal |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2113 REPAIR OR REPLACE STEAM TRAPS |
Savings: $5,375 Cost: $3,925 |
- | - | - | - | $5,375 | 1,426 | - | - | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$5,375 1,426 MMBtu |
- - Tgal |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $7,157 Cost: $5,079 |
$7,157 | 82,831 | - | - | - | - | - | - | - | - | - | - | - | - |
$7,157 82,831 kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $4,091 Cost: $4,108 |
- | - | - | - | $4,091 | 1,085 | - | - | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$4,091 1,085 MMBtu |
- - Tgal |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $14,919 Cost: $21,094 |
$12,653 | 146,443 | $2,266 | 150 | - | - | - | - | - | - | - | - | - | - |
$12,653 146,443 kWh |
$2,266 150 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.1131 REPAIR FAULTY INSULATION IN FURNACES, BOILERS, ETC |
Savings: $406 Cost: $1,040 |
- | - | - | - | $406 | 108 | - | - | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$406 108 MMBtu |
- - Tgal |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $2,993 Cost: $7,655 |
- | - | - | - | $2,993 | 794 | - | - | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$2,993 794 MMBtu |
- - Tgal |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $42,535 Cost: $127,175 |
$31,046 | 359,324 | $7,863 | 521 | - | - | - | - | $1,199 | - | - | - | $2,427 | - |
$31,046 359,324 kWh |
$7,863 521 kW-months/year |
- - MMBtu |
- - Tgal |
$1,199 - $ |
- - $ |
$2,427 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.3411 REPLACE ELECTRIC MOTORS WITH BACK PRESSURE STEAM TURBINES AND USE EXHAUST STEAM FOR PROCESS HEAT |
Savings: $104,307 Cost: $469,980 |
$82,366 | 953,313 | $21,941 | 1,455 | - | - | - | - | - | - | - | - | - | - |
$82,366 953,313 kWh |
$21,941 1,455 kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 3.4115 RECOVER AND REUSE COOLING WATER |
Savings: $4,700 Cost: $700 |
- | - | - | - | - | - | $4,700 | 3,916,538 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$4,700 3,916,538 Tgal |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 4.132 PURCHASE NEW EQUIPMENT TO REDUCE MATERIAL USE / COST |
Savings: $26,214 Cost: $85,490 |
- | - | - | - | - | - | - | - | - | - | $26,214 | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
- - $ |
$26,214 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $221,282 Cost: $726,246 |
$135,285 | 1,565,789 | $32,070 | 2,127 | $19,387 | 5,143 | $4,700 | 3,916,538 | $1,199 | - | $26,214 | - | $2,427 | - | $135,285 1,565,789 kWh |
$32,070 2,127 kW-months/year |
$19,387 5,143 MMBtu |
$4,700 3,916,538 Tgal |
$1,199 - $ |
$26,214 - $ |
$2,427 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $83,604 Cost: $165,697 |
$45,762 | 529,645 | $10,129 | 672 | $19,387 | 5,143 | $4,700 | 3,916,538 | $1,199 | - | - | - | $2,427 | - | $45,762 529,645 kWh |
$10,129 672 kW-months/year |
$19,387 5,143 MMBtu |
$4,700 3,916,538 Tgal |
$1,199 - $ |
- - $ |
$2,427 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Personnel Changes | Primary Raw Material | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Personnel Changes | Primary Raw Material | Ancillary Material Cost |