Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Francisco State University |
---|---|
Assessment Year | 2013 |
Principal Product | Paper Cups and Plastic Lids |
NAICS | 326199 - All Other Plastics Product Manufacturing |
SIC | 3089 - Plastics Products, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 200 |
Plant Area (Sq.Ft.) | 452,000 |
Annual Production | 60,000,000 Pounds |
Production Hrs. Annual | 8,760 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,355,870 | 19,406,067 | kWh | $0.07 |
Electricity Demand | $430,421 | 34,729 | kW-months/year | $12.39 |
Electricity Fees | $10,353 | - | $ | - |
Natural Gas | $114,492 | 16,176 | MMBtu | $7.08 |
TOTAL ENERGY COSTS | $1,911,136 | |||
RECOMMENDED SAVINGS* | $194,257 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $123,597 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Personnel Changes | Primary Raw Material | Electricity Usage | Electricity Demand | Personnel Changes | Primary Raw Material | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $7,213 Cost: - |
$7,213 | 103,228 | - | - | - | - | - | - |
$7,213 103,228 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $3,654 Cost: $436 |
$2,713 | 38,824 | $941 | 76 | - | - | - | - |
$2,713 38,824 kWh |
$941 76 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $34,286 Cost: $4,843 |
$25,935 | 371,194 | $8,351 | 674 | - | - | - | - |
$25,935 371,194 kWh |
$8,351 674 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $620 Cost: $359 |
$455 | 6,517 | $165 | 13 | - | - | - | - |
$455 6,517 kWh |
$165 13 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $52,879 Cost: $35,000 |
$46,613 | 667,135 | $6,266 | 505 | - | - | - | - |
$46,613 667,135 kWh |
$6,266 505 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $15,908 Cost: $12,499 |
$12,799 | 183,189 | $3,109 | 251 | - | - | - | - |
$12,799 183,189 kWh |
$3,109 251 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7144 INSTALL SPECTRAL REFLECTORS / DELAMP |
Savings: $3,902 Cost: $3,286 |
$2,626 | 37,580 | $1,276 | 103 | - | - | - | - |
$2,626 37,580 kWh |
$1,276 103 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $9,037 Cost: $10,104 |
$7,271 | 104,069 | $1,766 | 143 | - | - | - | - |
$7,271 104,069 kWh |
$1,766 143 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $10,058 Cost: $18,484 |
$10,058 | 143,951 | - | - | - | - | - | - |
$10,058 143,951 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $2,646 Cost: $8,690 |
$2,129 | 30,466 | $517 | 42 | - | - | - | - |
$2,129 30,466 kWh |
$517 42 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $6,030 Cost: $22,132 |
$4,852 | 69,446 | $1,178 | 95 | - | - | - | - |
$4,852 69,446 kWh |
$1,178 95 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $24,184 Cost: $91,986 |
$19,457 | 278,481 | $4,727 | 382 | - | - | - | - |
$19,457 278,481 kWh |
$4,727 382 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $4,151 Cost: $18,136 |
$3,415 | 48,882 | $551 | 44 | $222 | - | $(-37) | - |
$3,415 48,882 kWh |
$551 44 kW-months/year |
$222 - $ |
$(-37) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
14: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $370 Cost: $1,980 |
$370 | 5,301 | - | - | - | - | - | - |
$370 5,301 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
15: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD |
Savings: $19,319 Cost: $118,398 |
$15,815 | 226,343 | $3,504 | 283 | - | - | - | - |
$15,815 226,343 kWh |
$3,504 283 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $194,257 Cost: $346,333 |
$161,721 | 2,314,606 | $32,351 | 2,611 | $222 | - | $(-37) | - | $161,721 2,314,606 kWh |
$32,351 2,611 kW-months/year |
$222 - $ |
$(-37) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $123,597 Cost: $63,241 |
$102,999 | 1,474,156 | $20,598 | 1,662 | - | - | - | - | $102,999 1,474,156 kWh |
$20,598 1,662 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Personnel Changes | Primary Raw Material | Electricity Usage | Electricity Demand | Personnel Changes | Primary Raw Material |