Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Francisco State University |
---|---|
Assessment Year | 2017 |
Principal Product | wastewater, recycled water |
NAICS | 221320 - Sewage Treatment Facilities |
SIC | 4952 - Sewerage Systems |
Sales | $10,000,000-$50,000,000 |
# of Employees | 25 |
Plant Area (Sq.Ft.) | 741,826 |
Annual Production | 3,250,000 Thousand Gallons |
Production Hrs. Annual | 8,760 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $830,560 | 8,174,462 | kWh | $0.10 |
Electricity Demand | $337,325 | 15,086 | kW-months/year | $22.36 |
TOTAL ENERGY COSTS | $1,167,885 | |||
RECOMMENDED SAVINGS* | $207,474 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $26,126 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $852 Cost: $90 |
$655 | 6,446 | $197 | 9 | - | - | - | - | - | - |
$655 6,446 kWh |
$197 9 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $1,991 Cost: $546 |
$1,991 | 19,605 | - | - | - | - | - | - | - | - |
$1,991 19,605 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $22,454 Cost: $23,168 |
$19,293 | 189,893 | $3,505 | 157 | - | - | $1,585 | - | $(-1,929) | - |
$19,293 189,893 kWh |
$3,505 157 kW-months/year |
- - MMBtu |
$1,585 - $ |
$(-1,929) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,681 Cost: $3,001 |
$1,277 | 12,567 | $404 | 18 | - | - | - | - | - | - |
$1,277 12,567 kWh |
$404 18 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $6,437 Cost: $21,315 |
$4,947 | 48,690 | $1,490 | 67 | - | - | - | - | - | - |
$4,947 48,690 kWh |
$1,490 67 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4324 REPLACE HYDRAULIC / PNEUMATIC EQUIPMENT WITH ELECTRIC EQUIPMENT |
Savings: $4,855 Cost: $20,327 |
$4,855 | 47,785 | - | - | - | - | - | - | - | - |
$4,855 47,785 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.3415 USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT |
Savings: $169,204 Cost: $790,554 |
$272,383 | 2,680,938 | $82,397 | 3,685 | $(-59,003) | (-10,363) | $(-126,573) | - | - | - |
$272,383 2,680,938 kWh |
$82,397 3,685 kW-months/year |
$(-59,003) (-10,363) MMBtu |
$(-126,573) - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $207,474 Cost: $859,001 |
$305,401 | 3,005,924 | $87,993 | 3,936 | $(-59,003) | (-10,363) | $(-124,988) | - | $(-1,929) | - | $305,401 3,005,924 kWh |
$87,993 3,936 kW-months/year |
$(-59,003) (-10,363) MMBtu |
$(-124,988) - $ |
$(-1,929) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $26,126 Cost: $26,715 |
$22,561 | 222,065 | $3,909 | 175 | - | - | $1,585 | - | $(-1,929) | - | $22,561 222,065 kWh |
$3,909 175 kW-months/year |
- - MMBtu |
$1,585 - $ |
$(-1,929) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Ancillary Material Cost |