IAC logo
IAC Assessment: SF0577
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: SF0577
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Francisco State University
Assessment Year 2021
Principal Product Metal Containers
NAICS 332439 - Other Metal Container Manufacturing
SIC 3444 - Sheet Metalwork
Sales $5,000,000-$10,000,000
# of Employees 50
Plant Area (Sq.Ft.) 270,000
Annual Production 2,400 Units
Production Hrs. Annual 2,525
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $86,270 399,236 kWh $0.22
Electricity Demand $15,185 1,154 kW-months/year $13.16
Electricity Fees $8,724 - $ -
Natural Gas $812 48 MMBtu $17.09
LPG $11,811 475 MMBtu $24.88
TOTAL ENERGY COSTS $131,481
RECOMMENDED SAVINGS* $96,257 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $96,257
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Personnel Changes Ancillary Material Cost Electricity Usage Electricity Demand Personnel Changes Ancillary Material Cost
$ kWh $ kW-months/year $ $ $ $
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$3,483
Cost:
-
$4,100 18,359 $1,133 78 $(-1,750) - - - $4,100
18,359
kWh
$1,133
78
kW-months/year
$(-1,750)
-
$
-
-
$
02: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$141
Cost:
$62
$124 504 $17 1 - - - - $124
504
kWh
$17
1
kW-months/year
-
-
$
-
-
$
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$10,636
Cost:
$26,920
$7,340 32,870 $3,150 218 $338 - $(-192) - $7,340
32,870
kWh
$3,150
218
kW-months/year
$338
-
$
$(-192)
-
$
04: 2.4224 UPGRADE CONTROLS ON COMPRESSORS Savings:
$4,632
Cost:
$30,160
$3,629 16,252 $1,003 70 - - - - $3,629
16,252
kWh
$1,003
70
kW-months/year
-
-
$
-
-
$
05: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$77,365
Cost:
$283,655
$77,365 346,458 - - - - - - $77,365
346,458
kWh
-
-
kW-months/year
-
-
$
-
-
$
TOTAL RECOMMENDED Savings:
$96,257
Cost:
$340,797
$92,558 414,443 $5,303 367 $(-1,412) - $(-192) - $92,558
414,443
kWh
$5,303
367
kW-months/year
$(-1,412)
-
$
$(-192)
-
$
TOTAL IMPLEMENTED Savings:
$96,257
Cost:
$340,797
$92,558 414,443 $5,303 367 $(-1,412) - $(-192) - $92,558
414,443
kWh
$5,303
367
kW-months/year
$(-1,412)
-
$
$(-192)
-
$
Savings
Cost
$ kWh $ kW-months/year $ $ $ $
Electricity Usage Electricity Demand Personnel Changes Ancillary Material Cost Electricity Usage Electricity Demand Personnel Changes Ancillary Material Cost