Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Syracuse University |
---|---|
Assessment Year | 2008 |
Principal Product | Cable Connectors |
NAICS | 332721 - Precision Turned Product Manufacturing |
SIC | 3451 - Screw Machine Products |
Sales | $50,000,000-$100,000,000 |
# of Employees | 352 |
Plant Area (Sq.Ft.) | 106,000 |
Annual Production | 28,500,000 Pieces |
Production Hrs. Annual | 7,488 |
Location (State) | NY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $841,851 | 7,892,728 | kWh | $0.11 |
Electricity Demand | $247,684 | 14,227 | kW-months/year | $17.41 |
Natural Gas | $52,291 | 4,523 | MMBtu | $11.56 |
TOTAL ENERGY COSTS | $1,141,826 | |||
RECOMMENDED SAVINGS* | $65,389 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $50,727 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $31,297 Cost: - |
$24,838 | 232,129 | $6,459 | 371 |
$24,838 232,129 kWh |
$6,459 371 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $9,914 Cost: - |
$7,355 | 68,739 | $2,559 | 147 |
$7,355 68,739 kWh |
$2,559 147 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4314 USE SYNTHETIC LUBRICANT |
Savings: $4,440 Cost: - |
$3,413 | 31,899 | $1,027 | 59 |
$3,413 31,899 kWh |
$1,027 59 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,015 Cost: $200 |
$2,388 | 22,314 | $627 | 36 |
$2,388 22,314 kWh |
$627 36 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES |
Savings: $308 Cost: $444 |
$308 | 2,878 | - | - |
$308 2,878 kWh |
- - kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $16,415 Cost: $24,120 |
$13,020 | 121,680 | $3,395 | 195 |
$13,020 121,680 kWh |
$3,395 195 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $65,389 Cost: $24,764 |
$51,322 | 479,639 | $14,067 | 808 | $51,322 479,639 kWh |
$14,067 808 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $50,727 Cost: $24,320 |
$40,246 | 376,123 | $10,481 | 602 | $40,246 376,123 kWh |
$10,481 602 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand |