Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Syracuse University |
---|---|
Assessment Year | 2010 |
Principal Product | Automotive tire pressure sensors, Remote keyless entry devices |
NAICS | 336320 - Motor Vehicle Electrical and Electronic Equipment Manufacturing |
SIC | 3714 - Motor Vehicle Parts And Accessories |
Sales | $100,000,000-$500,000,000 |
# of Employees | 200 |
Plant Area (Sq.Ft.) | 72,051 |
Annual Production | 21,108,010 Pieces |
Production Hrs. Annual | 4,000 |
Location (State) | NY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $466,183 | 5,261,529 | kWh | $0.09 |
Electricity Demand | $97,541 | 11,628 | kW-months/year | $8.39 |
Electricity Fees | $5,387 | - | $ | - |
Natural Gas | $68,727 | 6,501 | MMBtu | $10.57 |
TOTAL ENERGY COSTS | $637,838 | |||
RECOMMENDED SAVINGS* | $34,756 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $27,702 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $13,013 Cost: - |
$13,013 | 143,000 | - | - | - | - | - | - |
$13,013 143,000 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $3,573 Cost: - |
$2,559 | 28,128 | $1,014 | 118 | - | - | - | - |
$2,559 28,128 kWh |
$1,014 118 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 4.821 PAY BILLS ON TIME TO AVOID LATE FEES |
Savings: $1,552 Cost: - |
- | - | - | - | - | - | $1,552 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$1,552 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $7,383 Cost: $578 |
$6,537 | 71,382 | $846 | 98 | - | - | - | - |
$6,537 71,382 kWh |
$846 98 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $3,787 Cost: $964 |
- | - | - | - | $3,787 | 343 | - | - |
- - kWh |
- - kW-months/year |
$3,787 343 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,653 Cost: $1,236 |
$1,653 | 18,168 | - | - | - | - | - | - |
$1,653 18,168 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES |
Savings: $528 Cost: $714 |
$528 | 5,798 | - | - | - | - | - | - |
$528 5,798 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,267 Cost: $8,373 |
$2,545 | 27,960 | $722 | 84 | - | - | - | - |
$2,545 27,960 kWh |
$722 84 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $34,756 Cost: $11,865 |
$26,835 | 294,436 | $2,582 | 300 | $3,787 | 343 | $1,552 | - | $26,835 294,436 kWh |
$2,582 300 kW-months/year |
$3,787 343 MMBtu |
$1,552 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $27,702 Cost: $2,528 |
$24,290 | 266,476 | $1,860 | 216 | - | - | $1,552 | - | $24,290 266,476 kWh |
$1,860 216 kW-months/year |
- - MMBtu |
$1,552 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost |