IAC logo
IAC Assessment: SU0374
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: SU0374
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Syracuse University
Assessment Year 2014
Principal Product CNC Tool Holders
NAICS 333517 - Machine Tool Manufacturing
SIC 3541 - Machine Tools, Metal Cutting Types
Sales $10,000,000-$50,000,000
# of Employees 123
Plant Area (Sq.Ft.) 80,000
Annual Production 240,000 Pieces
Production Hrs. Annual 6,240
Location (State) NY
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $108,925 3,784,050 kWh $0.03
Electricity Demand $38,460 7,497 kW-months/year $5.13
Natural Gas $4,886 616 MMBtu $7.93
TOTAL ENERGY COSTS $155,609
RECOMMENDED SAVINGS* $27,160 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $4,080
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Personnel Changes Electricity Usage Electricity Demand Natural Gas Personnel Changes
$ kWh $ kW-months/year $ MMBtu $ $
01: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS Savings:
$1,507
Cost:
-
- - - - $1,507 190 - - -
-
kWh
-
-
kW-months/year
$1,507
190
MMBtu
-
-
$
02: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$5,979
Cost:
$616
$5,979 207,604 - - - - - - $5,979
207,604
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$2,770
Cost:
$2,000
$2,770 96,195 - - - - - - $2,770
96,195
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$379
Cost:
$276
$68 2,365 $17 3 - - $294 - $68
2,365
kWh
$17
3
kW-months/year
-
-
MMBtu
$294
-
$
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$15,433
Cost:
$39,216
$11,908 413,472 $2,906 566 - - $619 - $11,908
413,472
kWh
$2,906
566
kW-months/year
-
-
MMBtu
$619
-
$
06: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS Savings:
$931
Cost:
$2,604
$(-135) (-4,680) $(-92) (-18) $1,158 146 - - $(-135)
(-4,680)
kWh
$(-92)
(-18)
kW-months/year
$1,158
146
MMBtu
-
-
$
07: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$161
Cost:
$615
$161 5,573 - - - - - - $161
5,573
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
TOTAL RECOMMENDED Savings:
$27,160
Cost:
$45,327
$20,751 720,529 $2,831 552 $2,665 336 $913 - $20,751
720,529
kWh
$2,831
552
kW-months/year
$2,665
336
MMBtu
$913
-
$
TOTAL IMPLEMENTED Savings:
$4,080
Cost:
$4,880
$2,703 93,880 $(-75) (-15) $1,158 146 $294 - $2,703
93,880
kWh
$(-75)
(-15)
kW-months/year
$1,158
146
MMBtu
$294
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $
Electricity Usage Electricity Demand Natural Gas Personnel Changes Electricity Usage Electricity Demand Natural Gas Personnel Changes