Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Syracuse University |
---|---|
Assessment Year | 2016 |
Principal Product | Blow Molded Plastic Parts |
NAICS | 326160 - Plastics Bottle Manufacturing |
SIC | 3085 - Plastics Bottles |
Sales | $10,000,000-$50,000,000 |
# of Employees | 67 |
Plant Area (Sq.Ft.) | 121,474 |
Annual Production | 14,000,000 Pieces |
Production Hrs. Annual | 8,400 |
Location (State) | NY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $731,001 | 16,242,225 | kWh | $0.05 |
Electricity Demand | $271,250 | 29,455 | kW-months/year | $9.21 |
Electricity Fees | $64,482 | - | $ | - |
Natural Gas | $48,163 | 8,500 | MMBtu | $5.67 |
TOTAL ENERGY COSTS | $1,116,196 | |||
RECOMMENDED SAVINGS* | $41,101 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $1,597 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7122 DISCONNECT BALLASTS |
Savings: $76 Cost: - |
$43 | 945 | $33 | 4 | - | - | - | - |
$43 945 kWh |
$33 4 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $22,191 Cost: $1,340 |
$22,191 | 493,136 | - | - | - | - | - | - |
$22,191 493,136 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $8,289 Cost: $737 |
$8,289 | 184,203 | - | - | - | - | - | - |
$8,289 184,203 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7314 REDUCE VENTILATION AIR |
Savings: $5,800 Cost: $523 |
$441 | 9,811 | $124 | 13 | $5,235 | 923 | - | - |
$441 9,811 kWh |
$124 13 kW-months/year |
$5,235 923 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 3.1161 ELIMINATE/REDUCE AN OPERATION |
Savings: $2,255 Cost: $1,215 |
$(-41) | (-912) | $(-332) | (-36) | - | - | $2,628 | - |
$(-41) (-912) kWh |
$(-332) (-36) kW-months/year |
- - MMBtu |
$2,628 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $231 Cost: $370 |
- | - | - | - | $231 | 41 | - | - |
- - kWh |
- - kW-months/year |
$231 41 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $219 Cost: $312 |
$110 | 2,453 | $31 | 3 | - | - | $78 | - |
$110 2,453 kWh |
$31 3 kW-months/year |
- - MMBtu |
$78 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS |
Savings: $181 Cost: $259 |
- | - | - | - | $181 | 32 | - | - |
- - kWh |
- - kW-months/year |
$181 32 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES |
Savings: $262 Cost: $591 |
$262 | 5,820 | - | - | - | - | - | - |
$262 5,820 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 4.821 PAY BILLS ON TIME TO AVOID LATE FEES |
Savings: $1,597 Cost: - |
- | - | - | - | - | - | $1,597 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$1,597 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $41,101 Cost: $5,347 |
$31,295 | 695,456 | $(-144) | (-16) | $5,647 | 996 | $4,303 | - | $31,295 695,456 kWh |
$(-144) (-16) kW-months/year |
$5,647 996 MMBtu |
$4,303 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $1,597 Cost: - |
- | - | - | - | - | - | $1,597 | - | - - kWh |
- - kW-months/year |
- - MMBtu |
$1,597 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost |