Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Syracuse University |
---|---|
Assessment Year | 2019 |
Principal Product | Ice Cream |
NAICS | 311520 - Ice Cream and Frozen Dessert Manufacturing |
SIC | 2024 - Ice Cream And Frozen Desserts |
Sales | $50,000,000-$100,000,000 |
# of Employees | 450 |
Plant Area (Sq.Ft.) | 250,000 |
Annual Production | 8,700 Thousand Gallons |
Production Hrs. Annual | 7,200 |
Location (State) | NY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,311,522 | 37,492,736 | kWh | $0.03 |
Electricity Demand | $1,031,809 | 73,453 | kW-months/year | $14.05 |
Electricity Fees | $78,764 | - | $ | - |
Natural Gas | $296,460 | 65,166 | MMBtu | $4.55 |
TOTAL ENERGY COSTS | $5,133,976 | |||
RECOMMENDED SAVINGS* | $26,631 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $13,476 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7122 DISCONNECT BALLASTS |
Savings: $2,630 Cost: - |
$1,580 | 45,144 | $1,050 | 75 | - | - | - | - | - | - |
$1,580 45,144 kWh |
$1,050 75 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $1,034 Cost: $28 |
- | - | - | - | $1,034 | 227 | - | - | - | - |
- - kWh |
- - kW-months/year |
$1,034 227 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $1,779 Cost: $1,023 |
- | - | - | - | $1,779 | 391 | - | - | - | - |
- - kWh |
- - kW-months/year |
$1,779 391 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $12,137 Cost: $13,202 |
$7,280 | 208,008 | $4,871 | 347 | - | - | - | - | $(-14) | - |
$7,280 208,008 kWh |
$4,871 347 kW-months/year |
- - MMBtu |
- - $ |
$(-14) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 3.1161 ELIMINATE/REDUCE AN OPERATION |
Savings: $1,649 Cost: $2,041 |
$(-14) | (-390) | $(-337) | (-24) | - | - | - | - | $2,000 | - |
$(-14) (-390) kWh |
$(-337) (-24) kW-months/year |
- - MMBtu |
- - $ |
$2,000 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $305 Cost: $360 |
$123 | 3,504 | $67 | 5 | - | - | $75 | - | $40 | - |
$123 3,504 kWh |
$67 5 kW-months/year |
- - MMBtu |
$75 - $ |
$40 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $640 Cost: $1,168 |
$640 | 18,288 | - | - | - | - | - | - | - | - |
$640 18,288 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $6,126 Cost: $15,784 |
- | - | - | - | $6,126 | 1,346 | - | - | - | - |
- - kWh |
- - kW-months/year |
$6,126 1,346 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES |
Savings: $331 Cost: $996 |
$331 | 9,471 | - | - | - | - | - | - | - | - |
$331 9,471 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $26,631 Cost: $34,602 |
$9,940 | 284,025 | $5,651 | 402 | $8,939 | 1,964 | $75 | - | $2,026 | - | $9,940 284,025 kWh |
$5,651 402 kW-months/year |
$8,939 1,964 MMBtu |
$75 - $ |
$2,026 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $13,476 Cost: $13,590 |
$7,403 | 211,512 | $4,938 | 351 | $1,034 | 227 | $75 | - | $26 | - | $7,403 211,512 kWh |
$4,938 351 kW-months/year |
$1,034 227 MMBtu |
$75 - $ |
$26 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | One-time Revenue or Avoided Cost |