Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Tennessee
Assessment Year 1988
Principal Product JUVENILE WOOD PRODUCTS
NAICS n/a
SIC 2511 - Wood Household Furniture
Sales $5,000,000-$10,000,000
# of Employees 195
Plant Area (Sq.Ft.) 0
Annual Production 152,000 Pieces
Production Hrs. Annual 3,163
Location (State) TN
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $95,857 1,126,905 kWh $0.09
Natural Gas $37,271 7,780 MMBtu $4.79
TOTAL ENERGY COSTS $133,128
RECOMMENDED SAVINGS* $42,438 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $30,853
#|Description Savings
Cost
Status Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes
$ kWh $ MMBtu $ $
01: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS Savings:
$1,038
Cost:
$18,500
$(-2,322) (-27,257) $3,360 700 - - $(-2,322)
(-27,257)
kWh
$3,360
700
MMBtu
-
-
$
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$13,104
Cost:
$750
$13,104 154,162 - - - - $13,104
154,162
kWh
-
-
MMBtu
-
-
$
03: 2.7123 KEEP LAMPS AND REFLECTORS CLEAN Savings:
$9,501
Cost:
$19,134
$9,093 106,975 - - $408 - $9,093
106,975
kWh
-
-
MMBtu
$408
-
$
04: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME Savings:
$10,015
Cost:
$4,840
$10,015 117,819 - - - - $10,015
117,819
kWh
-
-
MMBtu
-
-
$
05: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$3,400
Cost:
-
$3,400 39,859 - - - - $3,400
39,859
kWh
-
-
MMBtu
-
-
$
06: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$1,943
Cost:
$1,220
$1,943 22,860 - - - - $1,943
22,860
kWh
-
-
MMBtu
-
-
$
07: 2.7122 DISCONNECT BALLASTS Savings:
$1,320
Cost:
$2,321
$1,320 15,533 - - - - $1,320
15,533
kWh
-
-
MMBtu
-
-
$
08: 2.4312 IMPROVE LUBRICATION PRACTICES Savings:
$1,071
Cost:
-
$1,071 12,603 - - - - $1,071
12,603
kWh
-
-
MMBtu
-
-
$
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$1,046
Cost:
$360
$1,046 12,309 - - - - $1,046
12,309
kWh
-
-
MMBtu
-
-
$
TOTAL RECOMMENDED Savings:
$42,438
Cost:
$47,125
$38,670 454,863 $3,360 700 $408 - $38,670
454,863
kWh
$3,360
700
MMBtu
$408
-
$
TOTAL IMPLEMENTED Savings:
$30,853
Cost:
$9,131
$30,853 362,836 - - - - $30,853
362,836
kWh
-
-
MMBtu
-
-
$
Savings
Cost
$ kWh $ MMBtu $ $
Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes