Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Tennessee
Assessment Year 1989
Principal Product NYLON FIBERS
NAICS n/a
SIC 2281 - Yarn Spinning Mills
Sales $50,000,000-$100,000,000
# of Employees 430
Plant Area (Sq.Ft.) 0
Annual Production 40,000,000 Pounds
Production Hrs. Annual 8,400
Location (State) VA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $1,156,378 26,793,963 kWh $0.04
Natural Gas $139,231 32,844 MMBtu $4.24
TOTAL ENERGY COSTS $1,295,609
RECOMMENDED SAVINGS* $224,464 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $215,592
#|Description Savings
Cost
Status Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes
$ kWh $ MMBtu $ $
01: 2.7123 KEEP LAMPS AND REFLECTORS CLEAN Savings:
$99,672
Cost:
$103,100
$92,112 2,142,145 - - $7,560 - $92,112
2,142,145
kWh
-
-
MMBtu
$7,560
-
$
02: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES Savings:
$18,992
Cost:
$33,000
- - $18,992 4,522 - - -
-
kWh
$18,992
4,522
MMBtu
-
-
$
03: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$37,026
Cost:
$7,500
$37,026 861,079 - - - - $37,026
861,079
kWh
-
-
MMBtu
-
-
$
04: 2.2163 USE MINIMUM STEAM OPERATING PRESSURE Savings:
$8,371
Cost:
-
- - $8,371 1,993 - - -
-
kWh
$8,371
1,993
MMBtu
-
-
$
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$19,811
Cost:
-
$19,811 460,727 - - - - $19,811
460,727
kWh
-
-
MMBtu
-
-
$
06: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS Savings:
$13,951
Cost:
$240
$13,006 302,462 - - $945 - $13,006
302,462
kWh
-
-
MMBtu
$945
-
$
07: 2.4312 IMPROVE LUBRICATION PRACTICES Savings:
$8,872
Cost:
$4,060
$8,872 206,331 - - - - $8,872
206,331
kWh
-
-
MMBtu
-
-
$
08: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$8,431
Cost:
$1,800
$8,431 196,073 - - - - $8,431
196,073
kWh
-
-
MMBtu
-
-
$
09: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$2,759
Cost:
$1,500
- - $2,759 657 - - -
-
kWh
$2,759
657
MMBtu
-
-
$
10: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$6,579
Cost:
$4,050
$6,579 152,989 - - - - $6,579
152,989
kWh
-
-
MMBtu
-
-
$
TOTAL RECOMMENDED Savings:
$224,464
Cost:
$155,250
$185,837 4,321,806 $30,122 7,172 $8,505 - $185,837
4,321,806
kWh
$30,122
7,172
MMBtu
$8,505
-
$
TOTAL IMPLEMENTED Savings:
$215,592
Cost:
$151,190
$176,965 4,115,475 $30,122 7,172 $8,505 - $176,965
4,115,475
kWh
$30,122
7,172
MMBtu
$8,505
-
$
Savings
Cost
$ kWh $ MMBtu $ $
Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes