Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Tennessee |
---|---|
Assessment Year | 1998 |
Principal Product | High density polyethylene conduit and water pipe |
NAICS | n/a |
SIC | 3084 - Plastics Pipe |
Sales | $10,000,000-$50,000,000 |
# of Employees | 120 |
Plant Area (Sq.Ft.) | 112,500 |
Annual Production | 30,000,000 Pounds |
Production Hrs. Annual | 8,400 |
Location (State) | KY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $270,435 | 9,299,531 | kWh | $0.03 |
Electricity Demand | $66,127 | 15,710 | kW-months/year | $4.21 |
Electricity Fees | $73,851 | - | $ | - |
Natural Gas | $10,756 | 1,329 | MMBtu | $8.09 |
TOTAL ENERGY COSTS | $421,169 | |||
RECOMMENDED SAVINGS* | $439,485 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $53,400 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | Administrative Changes | Primary Product | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | Administrative Changes | Primary Product | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 3.5215 AVOID CONTAMINATION OF END PIECES AND REUSE AS FEED STOCK |
Savings: $363,750 Cost: $20,000 |
- | - | - | - | - | - | - | - | $(-30,000) | - | $393,750 | - |
- - kWh |
- - kW-months/year |
- - $ |
- - $ |
$(-30,000) - $ |
$393,750 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 3.1191 CHANGE PROCEDURES / EQUIPMENT / OPERATING CONDITIONS |
Savings: $32,370 Cost: $50,000 |
- | - | - | - | - | - | $(-20,000) | - | - | - | $52,370 | - |
- - kWh |
- - kW-months/year |
- - $ |
$(-20,000) - $ |
- - $ |
$52,370 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 4.611 BEGIN A PRACTICE OF PREDICTIVE / PREVENTATIVE MAINTENANCE |
Savings: $17,850 Cost: $32,200 |
- | - | - | - | - | - | - | - | - | - | $17,850 | - |
- - kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
$17,850 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $11,910 Cost: $1,440 |
- | - | - | - | $11,910 | - | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$11,910 - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING |
Savings: $7,575 Cost: $8,575 |
$6,880 | 275,205 | $695 | 165 | - | - | - | - | - | - | - | - |
$6,880 275,205 kWh |
$695 165 kW-months/year |
- - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $3,180 Cost: $2,030 |
$2,020 | 80,891 | $1,160 | 276 | - | - | - | - | - | - | - | - |
$2,020 80,891 kWh |
$1,160 276 kW-months/year |
- - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $2,850 Cost: $1,100 |
$2,290 | 91,735 | $560 | 132 | - | - | - | - | - | - | - | - |
$2,290 91,735 kWh |
$560 132 kW-months/year |
- - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $439,485 Cost: $115,345 |
$11,190 | 447,831 | $2,415 | 573 | $11,910 | - | $(-20,000) | - | $(-30,000) | - | $463,970 | - | $11,190 447,831 kWh |
$2,415 573 kW-months/year |
$11,910 - $ |
$(-20,000) - $ |
$(-30,000) - $ |
$463,970 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $53,400 Cost: $84,230 |
$2,020 | 80,891 | $1,160 | 276 | - | - | $(-20,000) | - | - | - | $70,220 | - | $2,020 80,891 kWh |
$1,160 276 kW-months/year |
- - $ |
$(-20,000) - $ |
- - $ |
$70,220 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | Administrative Changes | Primary Product | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | Administrative Changes | Primary Product |