Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Texas Rio Grande Valley |
---|---|
Assessment Year | 2017 |
Principal Product | Valves |
NAICS | 332911 - Industrial Valve Manufacturing |
SIC | 3491 - Industrial Valves |
Sales | $1,000,000-$5,000,000 |
# of Employees | 113 |
Plant Area (Sq.Ft.) | 101,000 |
Annual Production | 50,000 Units |
Production Hrs. Annual | 2,016 |
Location (State) | TX |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $278,011 | 3,169,440 | kWh | $0.09 |
Electricity Demand | $3,191 | 968 | kW-months/year | $3.30 |
Natural Gas | $1,131 | 102 | MMBtu | $11.09 |
TOTAL ENERGY COSTS | $282,333 | |||
RECOMMENDED SAVINGS* | $56,304 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $51,161 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Administrative Changes | Primary Raw Material | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Administrative Changes | Primary Raw Material | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.8121 APPLY FOR TAX-FREE STATUS FOR ENERGY PURCHASES |
Savings: $19,042 Cost: $5,000 |
- | - | - | - | $19,042 | - | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$19,042 - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $6,935 Cost: $23,676 |
$5,946 | 67,569 | $989 | 293 | - | - | - | - | - | - | - | - |
$5,946 67,569 kWh |
$989 293 kW-months/year |
- - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7121 UTILIZE DAYLIGHT WHENEVER POSSIBLE IN LIEU OF ARTIFICIAL LIGHT |
Savings: $112 Cost: - |
$112 | 1,277 | - | - | - | - | - | - | - | - | - | - |
$112 1,277 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $441 Cost: $237 |
$126 | 1,430 | $7 | 2 | - | - | $72 | - | - | - | $237 | - |
$126 1,430 kWh |
$7 2 kW-months/year |
- - $ |
$72 - $ |
- - $ |
$237 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 3.2123 CONVERT TO HIGH VOLUME LOW PRESSURE (HVLP) PAINT GUNS |
Savings: $5,143 Cost: $50 |
- | - | - | - | - | - | - | - | $5,143 | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
- - $ |
$5,143 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7495 INSTALL REPLACEMENT DOORS |
Savings: $9,766 Cost: $5,000 |
$9,766 | 110,976 | - | - | - | - | - | - | - | - | - | - |
$9,766 110,976 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $13,442 Cost: $2,500 |
$11,522 | 130,928 | $1,920 | 568 | - | - | - | - | - | - | - | - |
$11,522 130,928 kWh |
$1,920 568 kW-months/year |
- - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $1,422 Cost: $6 |
$1,220 | 13,860 | $203 | 60 | - | - | - | - | - | - | - | - |
$1,220 13,860 kWh |
$203 60 kW-months/year |
- - $ |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $56,304 Cost: $36,469 |
$28,691 | 326,039 | $3,119 | 923 | $19,042 | - | $72 | - | $5,143 | - | $237 | - | $28,691 326,039 kWh |
$3,119 923 kW-months/year |
$19,042 - $ |
$72 - $ |
$5,143 - $ |
$237 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $51,161 Cost: $36,419 |
$28,691 | 326,039 | $3,119 | 923 | $19,042 | - | $72 | - | - | - | $237 | - | $28,691 326,039 kWh |
$3,119 923 kW-months/year |
$19,042 - $ |
$72 - $ |
- - $ |
$237 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Administrative Changes | Primary Raw Material | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Administrative Changes | Primary Raw Material | Ancillary Material Cost |