Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Tennessee Technological University |
---|---|
Assessment Year | 2015 |
Principal Product | Marine Power Systems |
NAICS | 333618 - Other Engine Equipment Manufacturing |
SIC | 3519 - Internal Combustion Engines, Nec |
Sales | $100,000,000-$500,000,000 |
# of Employees | 117 |
Plant Area (Sq.Ft.) | 213,260 |
Annual Production | 6,500 Pieces |
Production Hrs. Annual | 4,200 |
Location (State) | TN |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $277,629 | 4,262,400 | kWh | $0.07 |
Electricity Demand | $206,516 | 16,696 | kW-months/year | $12.37 |
Natural Gas | $133,010 | 24,838 | MMBtu | $5.36 |
TOTAL ENERGY COSTS | $628,230 | |||
RECOMMENDED SAVINGS* | $56,911 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $24,151 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1133 ADJUST BURNERS FOR EFFICIENT OPERATION |
Savings: $12,531 Cost: $1,500 |
- | - | - | - | $12,531 | 2,340 |
- - kWh |
- - kW-months/year |
$12,531 2,340 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $11,633 Cost: $6,247 |
$11,633 | 178,969 | - | - | - | - |
$11,633 178,969 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $3,904 Cost: $740 |
$3,904 | 60,067 | - | - | - | - |
$3,904 60,067 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $3,662 Cost: $8,000 |
$2,376 | 36,554 | $1,286 | 104 | - | - |
$2,376 36,554 kWh |
$1,286 104 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $8,830 Cost: $1,514 |
$8,830 | 135,846 | - | - | - | - |
$8,830 135,846 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $4,084 Cost: $3,000 |
$2,649 | 40,758 | $1,435 | 116 | - | - |
$2,649 40,758 kWh |
$1,435 116 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $10,606 Cost: $2,440 |
$10,606 | 163,170 | - | - | - | - |
$10,606 163,170 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $755 Cost: $440 |
$755 | 11,613 | - | - | - | - |
$755 11,613 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7122 DISCONNECT BALLASTS |
Savings: $275 Cost: $90 |
$218 | 3,351 | $57 | 5 | - | - |
$218 3,351 kWh |
$57 5 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $384 Cost: $804 |
$384 | 5,906 | - | - | - | - |
$384 5,906 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $247 Cost: $1,200 |
$160 | 2,457 | $87 | 7 | - | - |
$160 2,457 kWh |
$87 7 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $56,911 Cost: $25,975 |
$41,515 | 638,691 | $2,865 | 232 | $12,531 | 2,340 | $41,515 638,691 kWh |
$2,865 232 kW-months/year |
$12,531 2,340 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $24,151 Cost: $8,958 |
$22,629 | 348,137 | $1,522 | 123 | - | - | $22,629 348,137 kWh |
$1,522 123 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |