Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Tennessee Technological University
Assessment Year 2022
Principal Product Exterior Automotive Mirrors
NAICS 336111 - Automobile Manufacturing
SIC 3711 - Motor Vehicles And Car Bodies
Sales $100,000,000-$500,000,000
# of Employees 650
Plant Area (Sq.Ft.) 310,000
Annual Production 32,825,809 Units
Production Hrs. Annual 8,400
Location (State) TN
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $673,037 15,873,707 kWh $0.04
Electricity Demand $329,942 27,282 kW-months/year $12.09
Natural Gas $513,573 49,773 MMBtu $10.32
TOTAL ENERGY COSTS $1,580,599
RECOMMENDED SAVINGS* $328,993 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $72,599
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Water Disposal Electricity Usage Electricity Demand Natural Gas Water Disposal
$ kWh $ kW-months/year $ MMBtu $ Tgal
01: 2.3415 USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT Savings:
$197,305
Cost:
$1,241,200
$152,425 3,594,939 $62,094 5,136 $(-17,214) (-1,668) - - $152,425
3,594,939
kWh
$62,094
5,136
kW-months/year
$(-17,214)
(-1,668)
MMBtu
-
-
Tgal
02: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME Savings:
$65,016
Cost:
$5,000
- - - - $65,016 6,300 - - -
-
kWh
-
-
kW-months/year
$65,016
6,300
MMBtu
-
-
Tgal
03: 2.2511 INSULATE BARE EQUIPMENT Savings:
$51,693
Cost:
$8,551
- - - - $51,693 5,009 - - -
-
kWh
-
-
kW-months/year
$51,693
5,009
MMBtu
-
-
Tgal
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$6,155
Cost:
$2,860
$6,155 145,165 - - - - - - $6,155
145,165
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
05: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME Savings:
$3,192
Cost:
$2,000
- - $3,192 264 - - - - -
-
kWh
$3,192
264
kW-months/year
-
-
MMBtu
-
-
Tgal
06: 3.4116 METER RECYCLED WATER (TO REDUCE SEWER CHARGES) Savings:
$1,707
Cost:
$400
- - - - - - $1,707 281 -
-
kWh
-
-
kW-months/year
-
-
MMBtu
$1,707
281
Tgal
07: 2.2511 INSULATE BARE EQUIPMENT Savings:
$1,084
Cost:
$428
- - - - $1,084 105 - - -
-
kWh
-
-
kW-months/year
$1,084
105
MMBtu
-
-
Tgal
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$1,072
Cost:
$1,926
$762 17,976 $310 26 - - - - $762
17,976
kWh
$310
26
kW-months/year
-
-
MMBtu
-
-
Tgal
09: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$780
Cost:
$2,250
$551 13,007 $229 19 - - - - $551
13,007
kWh
$229
19
kW-months/year
-
-
MMBtu
-
-
Tgal
10: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$633
Cost:
$1,500
$447 10,537 $186 15 - - - - $447
10,537
kWh
$186
15
kW-months/year
-
-
MMBtu
-
-
Tgal
11: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME Savings:
$356
Cost:
$700
$356 8,400 - - - - - - $356
8,400
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
Tgal
TOTAL RECOMMENDED Savings:
$328,993
Cost:
$1,266,815
$160,696 3,790,024 $66,011 5,460 $100,579 9,746 $1,707 281 $160,696
3,790,024
kWh
$66,011
5,460
kW-months/year
$100,579
9,746
MMBtu
$1,707
281
Tgal
TOTAL IMPLEMENTED Savings:
$72,599
Cost:
$10,486
$7,273 171,541 $310 26 $65,016 6,300 - - $7,273
171,541
kWh
$310
26
kW-months/year
$65,016
6,300
MMBtu
-
-
Tgal
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ Tgal
Electricity Usage Electricity Demand Natural Gas Water Disposal Electricity Usage Electricity Demand Natural Gas Water Disposal