Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Alabama
Assessment Year 2017
Principal Product Automobiles
NAICS 336112 - Light Truck and Utility Vehicle Manufacturing
SIC 3711 - Motor Vehicles And Car Bodies
Sales >$500,000,000
# of Employees 4,600
Plant Area (Sq.Ft.) 3,736,000
Annual Production 366,000 Units
Production Hrs. Annual 5,000
Location (State) AL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $18,604,216 292,105,926 kWh $0.06
Natural Gas $3,417,235 1,018,864 MMBtu $3.35
TOTAL ENERGY COSTS $22,021,451
RECOMMENDED SAVINGS* $550,748 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $56,190
#|Description Savings
Cost
Status Electricity Usage Natural Gas Electricity Usage Natural Gas
$ kWh $ MMBtu
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$435,778
Cost:
$988,290
$435,778 6,841,100 - - $435,778
6,841,100
kWh
-
-
MMBtu
02: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$21,405
Cost:
$588
$21,405 336,084 - - $21,405
336,084
kWh
-
-
MMBtu
03: 2.2425 USE FLUE GASES TO HEAT PROCESS OR SERVICE WATER Savings:
$49,747
Cost:
$100,000
$(-237) (-3,728) $49,984 14,693 $(-237)
(-3,728)
kWh
$49,984
14,693
MMBtu
04: 2.2511 INSULATE BARE EQUIPMENT Savings:
$221
Cost:
$564
- - $221 66 -
-
kWh
$221
66
MMBtu
05: 2.2211 USE OPTIMUM TEMPERATURE Savings:
$33,738
Cost:
$8,460
- - $33,738 10,059 -
-
kWh
$33,738
10,059
MMBtu
06: 2.7233 USE PROPERLY DESIGNED AND SIZED HVAC EQUIPMENT Savings:
$826
Cost:
$2,820
$826 12,963 - - $826
12,963
kWh
-
-
MMBtu
07: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$9,033
Cost:
$42,204
$9,033 141,834 - - $9,033
141,834
kWh
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$550,748
Cost:
$1,142,926
$466,805 7,328,253 $83,943 24,818 $466,805
7,328,253
kWh
$83,943
24,818
MMBtu
TOTAL IMPLEMENTED Savings:
$56,190
Cost:
$12,432
$22,231 349,047 $33,959 10,125 $22,231
349,047
kWh
$33,959
10,125
MMBtu
Savings
Cost
$ kWh $ MMBtu