Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Alabama |
---|---|
Assessment Year | 2017 |
Principal Product | Refurbished military Vehicles |
NAICS | 336120 - Heavy Duty Truck Manufacturing |
SIC | 3711 - Motor Vehicles And Car Bodies |
Sales | $10,000,000-$50,000,000 |
# of Employees | 150 |
Plant Area (Sq.Ft.) | 215,000 |
Annual Production | 106 Units |
Production Hrs. Annual | 2,000 |
Location (State) | AL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $163,776 | 1,267,575 | kWh | $0.13 |
Electricity Demand | $36,076 | 7,690 | kW-months/year | $4.69 |
Electricity Fees | $9,572 | - | $ | - |
Natural Gas | $23,214 | 2,487 | MMBtu | $9.33 |
TOTAL ENERGY COSTS | $232,638 | |||
RECOMMENDED SAVINGS* | $36,157 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $10,790 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Electricity Usage | Electricity Demand | Electricity Fees | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $12,372 Cost: $25,579 |
$9,878 | 77,378 | $2,158 | 460 | $336 | - |
$9,878 77,378 kWh |
$2,158 460 kW-months/year |
$336 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $1,034 Cost: $830 |
$1,006 | 7,787 | - | - | $28 | - |
$1,006 7,787 kWh |
- - kW-months/year |
$28 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $9,904 Cost: $900 |
$9,635 | 74,571 | - | - | $269 | - |
$9,635 74,571 kWh |
- - kW-months/year |
$269 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $3,091 Cost: $500 |
$2,519 | 19,496 | $488 | 104 | $84 | - |
$2,519 19,496 kWh |
$488 104 kW-months/year |
$84 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $9,414 Cost: $4,645 |
$7,929 | 61,370 | $1,229 | 262 | $256 | - |
$7,929 61,370 kWh |
$1,229 262 kW-months/year |
$256 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $342 Cost: $85 |
$262 | 1,998 | $71 | 15 | $9 | - |
$262 1,998 kWh |
$71 15 kW-months/year |
$9 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $36,157 Cost: $32,539 |
$31,229 | 242,600 | $3,946 | 841 | $982 | - | $31,229 242,600 kWh |
$3,946 841 kW-months/year |
$982 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $10,790 Cost: $5,560 |
$9,197 | 71,155 | $1,300 | 277 | $293 | - | $9,197 71,155 kWh |
$1,300 277 kW-months/year |
$293 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Electricity Usage | Electricity Demand | Electricity Fees |