Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Alabama |
---|---|
Assessment Year | 2022 |
Principal Product | Automotive Trim |
NAICS | 326199 - All Other Plastics Product Manufacturing |
SIC | 3714 - Motor Vehicle Parts And Accessories |
Sales | $50,000,000-$100,000,000 |
# of Employees | 325 |
Plant Area (Sq.Ft.) | 293,000 |
Annual Production | 3,000,000 Units |
Production Hrs. Annual | 6,336 |
Location (State) | AL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $767,332 | 13,235,611 | kWh | $0.06 |
Electricity Demand | $122,149 | 29,821 | kW-months/year | $4.10 |
Electricity Fees | $71,163 | - | $ | - |
Natural Gas | $1,836 | 124 | MMBtu | $14.81 |
TOTAL ENERGY COSTS | $962,480 | |||
RECOMMENDED SAVINGS* | $59,736 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $52,826 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Electricity Usage | Electricity Demand | Electricity Fees | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $46,023 Cost: $44,464 |
$37,494 | 646,789 | $5,120 | 1,225 | $3,409 | - |
$37,494 646,789 kWh |
$5,120 1,225 kW-months/year |
$3,409 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $2,699 Cost: $2,060 |
$2,499 | 43,110 | - | - | $200 | - |
$2,499 43,110 kWh |
- - kW-months/year |
$200 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $4,104 Cost: $4,929 |
$3,470 | 59,865 | $330 | 79 | $304 | - |
$3,470 59,865 kWh |
$330 79 kW-months/year |
$304 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $6,910 Cost: $400 |
$5,767 | 99,475 | $631 | 151 | $512 | - |
$5,767 99,475 kWh |
$631 151 kW-months/year |
$512 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $59,736 Cost: $51,853 |
$49,230 | 849,239 | $6,081 | 1,455 | $4,425 | - | $49,230 849,239 kWh |
$6,081 1,455 kW-months/year |
$4,425 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $52,826 Cost: $51,453 |
$43,463 | 749,764 | $5,450 | 1,304 | $3,913 | - | $43,463 749,764 kWh |
$5,450 1,304 kW-months/year |
$3,913 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Electricity Usage | Electricity Demand | Electricity Fees |