IAC logo
IAC Assessment: UD0047
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: UD0047
IAC Center University of Dayton
Assessment Year 1982
Principal Product MEN'S/WOMEN'S SUITS
NAICS n/a
SIC 2311 - Men's and Boys' Suits, Coats, and Overcoats
Sales $5,000,000-$10,000,000
# of Employees 330
Plant Area (Sq.Ft.) 0
Annual Production 30,000 Pieces
Production Hrs. Annual 1,600
Location (State) OH
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $85,247 1,002,345 kWh $0.09
Natural Gas $51,204 13,859 MMBtu $3.69
Fuel Oil #2 $4,600 700 MMBtu $6.57
TOTAL ENERGY COSTS $141,051
RECOMMENDED SAVINGS* $17,314 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Natural Gas Fuel Oil #2 Electricity Usage Natural Gas Fuel Oil #2
$ kWh $ MMBtu $ MMBtu
01: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$3,843
Cost:
$600
- - $3,600 732 $243 37 -
-
kWh
$3,600
732
MMBtu
$243
37
MMBtu
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$2,175
Cost:
$122
$2,440 27,843 $(-265) (-54) - - $2,440
27,843
kWh
$(-265)
(-54)
MMBtu
-
-
MMBtu
03: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES Savings:
$4,878
Cost:
$2,288
$2,362 24,033 $2,516 511 - - $2,362
24,033
kWh
$2,516
511
MMBtu
-
-
MMBtu
04: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES Savings:
$1,352
Cost:
$1,500
$678 6,741 $674 137 - - $678
6,741
kWh
$674
137
MMBtu
-
-
MMBtu
05: 2.7494 INSTALL STORM WINDOWS AND DOORS Savings:
$5,066
Cost:
$6,048
- - $5,066 1,030 - - -
-
kWh
$5,066
1,030
MMBtu
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$17,314
Cost:
$10,558
$5,480 58,617 $11,591 2,356 $243 37 $5,480
58,617
kWh
$11,591
2,356
MMBtu
$243
37
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
MMBtu
-
-
MMBtu
Savings
Cost
$ kWh $ MMBtu $ MMBtu
Electricity Usage Natural Gas Fuel Oil #2 Electricity Usage Natural Gas Fuel Oil #2