Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Dayton
Assessment Year 1990
Principal Product PAPERBOARD CARTONS
NAICS n/a
SIC 2657 - Folding Paperboard Boxes
Sales $10,000,000-$50,000,000
# of Employees 146
Plant Area (Sq.Ft.) 0
Annual Production 42,000 Tons
Production Hrs. Annual 8,736
Location (State) IN
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $312,453 6,454,865 kWh $0.05
Natural Gas $187,138 50,380 MMBtu $3.71
TOTAL ENERGY COSTS $499,591
RECOMMENDED SAVINGS* $69,885 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $26,391
#|Description Savings
Cost
Status Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes
$ kWh $ MMBtu $ $
01: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$8,661
Cost:
$5,500
$8,661 105,803 - - - - $8,661
105,803
kWh
-
-
MMBtu
-
-
$
02: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$9,752
Cost:
$11,000
$9,752 242,087 - - - - $9,752
242,087
kWh
-
-
MMBtu
-
-
$
03: 2.7141 LOWER LIGHT FIXTURES IN HIGH CEILING AREAS Savings:
$1,240
Cost:
$300
$1,483 33,118 $(-243) (-81) - - $1,483
33,118
kWh
$(-243)
(-81)
MMBtu
-
-
$
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$9,774
Cost:
$27,775
$10,536 262,896 $(-1,346) (-449) $584 - $10,536
262,896
kWh
$(-1,346)
(-449)
MMBtu
$584
-
$
05: 2.2492 USE "HEAT WHEEL" OR OTHER HEAT EXCHANGER TO CROSS-EXCHANGE BUILDING EXHAUST AIR WITH MAKE-UP AIR Savings:
$32,480
Cost:
$60,000
- - $32,480 10,827 - - -
-
kWh
$32,480
10,827
MMBtu
-
-
$
06: 2.2443 RE-USE OR RECYCLE HOT OR COLD PROCESS EXHAUST AIR Savings:
$7,978
Cost:
$20,000
- - $7,978 2,659 - - -
-
kWh
$7,978
2,659
MMBtu
-
-
$
TOTAL RECOMMENDED Savings:
$69,885
Cost:
$124,575
$30,432 643,904 $38,869 12,956 $584 - $30,432
643,904
kWh
$38,869
12,956
MMBtu
$584
-
$
TOTAL IMPLEMENTED Savings:
$26,391
Cost:
$36,500
$18,413 347,890 $7,978 2,659 - - $18,413
347,890
kWh
$7,978
2,659
MMBtu
-
-
$
Savings
Cost
$ kWh $ MMBtu $ $
Electricity Usage Natural Gas Administrative Changes Electricity Usage Natural Gas Administrative Changes