Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Dayton |
---|---|
Assessment Year | 2003 |
Principal Product | Plastic Wheel Covers and Bezels |
NAICS | 326199 - All Other Plastics Product Manufacturing |
SIC | 3089 - Plastics Products, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 153 |
Plant Area (Sq.Ft.) | 79,106 |
Annual Production | 5,400,000 Pieces |
Production Hrs. Annual | 7,056 |
Location (State) | OH |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $185,821 | 6,987,875 | kWh | $0.03 |
Electricity Demand | $162,594 | 13,716 | kW-months/year | $11.85 |
Natural Gas | $192,875 | 25,091 | MMBtu | $7.69 |
TOTAL ENERGY COSTS | $543,911 | |||
RECOMMENDED SAVINGS* | $32,672 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $12,435 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $9,320 Cost: $4,000 |
- | - | - | - | $9,320 | 1,215 |
- - kWh |
- - kW-months/year |
$9,320 1,215 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $7,300 Cost: $5,520 |
$6,055 | 232,850 | $1,245 | 96 | - | - |
$6,055 232,850 kWh |
$1,245 96 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $6,440 Cost: $20,540 |
$3,485 | 134,065 | $2,955 | 228 | - | - |
$3,485 134,065 kWh |
$2,955 228 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $2,218 Cost: - |
$1,285 | 49,390 | $933 | 74 | - | - |
$1,285 49,390 kWh |
$933 74 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $1,644 Cost: $3,620 |
$1,284 | 49,373 | $360 | 28 | - | - |
$1,284 49,373 kWh |
$360 28 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7122 DISCONNECT BALLASTS |
Savings: $1,597 Cost: $144 |
$925 | 35,562 | $672 | 52 | - | - |
$925 35,562 kWh |
$672 52 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7122 DISCONNECT BALLASTS |
Savings: $1,367 Cost: $70 |
$792 | 30,458 | $575 | 44 | - | - |
$792 30,458 kWh |
$575 44 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $1,243 Cost: $2,500 |
- | - | - | - | $1,243 | 162 |
- - kWh |
- - kW-months/year |
$1,243 162 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $813 Cost: $1,458 |
$471 | 18,110 | $342 | 26 | - | - |
$471 18,110 kWh |
$342 26 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $730 Cost: $160 |
$367 | 14,112 | $363 | 24 | - | - |
$367 14,112 kWh |
$363 24 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $32,672 Cost: $38,012 |
$14,664 | 563,920 | $7,445 | 572 | $10,563 | 1,377 | $14,664 563,920 kWh |
$7,445 572 kW-months/year |
$10,563 1,377 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $12,435 Cost: $22,212 |
$6,958 | 267,585 | $5,477 | 424 | - | - | $6,958 267,585 kWh |
$5,477 424 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |