Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Dayton |
---|---|
Assessment Year | 2005 |
Principal Product | Caddy Fasteners |
NAICS | 339993 - Fastener, Button, Needle, and Pin Manufacturing |
SIC | 3965 - Fasteners, Buttons, Needles, & Pins |
Sales | $10,000,000-$50,000,000 |
# of Employees | 224 |
Plant Area (Sq.Ft.) | 170,000 |
Annual Production | 336,000,000 Pieces |
Production Hrs. Annual | 6,240 |
Location (State) | OH |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $311,251 | 6,080,813 | kWh | $0.05 |
Electricity Demand | $160,822 | 11,604 | kW-months/year | $13.86 |
Natural Gas | $386,197 | 41,720 | MMBtu | $9.26 |
TOTAL ENERGY COSTS | $905,568 | |||
RECOMMENDED SAVINGS* | $127,589 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $17,921 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Water Disposal | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Water Disposal | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | Tgal | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $40,357 Cost: $3,600 |
$9,840 | 519,920 | $30,517 | 996 | - | - | - | - | - | - | - | - |
$9,840 519,920 kWh |
$30,517 996 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $29,475 Cost: $7,200 |
$6,971 | 366,912 | $21,620 | 708 | - | - | - | - | - | - | $884 | - |
$6,971 366,912 kWh |
$21,620 708 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
$884 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2312 MINIMIZE NON-ESSENTIAL MATERIAL IN HEAT TREATMENT PROCESS |
Savings: $13,381 Cost: $25,000 |
- | - | - | - | - | - | $13,381 | 1,445 | - | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$13,381 1,445 MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2514 COVER OPEN TANKS |
Savings: $12,069 Cost: $2,170 |
- | - | - | - | - | - | $11,149 | 1,204 | $920 | 108,475 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$11,149 1,204 MMBtu |
$920 108,475 Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $6,473 Cost: $12,880 |
- | - | - | - | - | - | $6,473 | 699 | - | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$6,473 699 MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $5,769 Cost: $4,350 |
- | - | - | - | - | - | $5,769 | 623 | - | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$5,769 623 MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $4,376 Cost: $1,000 |
$1,067 | 56,160 | $3,309 | 108 | - | - | - | - | - | - | - | - |
$1,067 56,160 kWh |
$3,309 108 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $4,232 Cost: $9,916 |
$588 | 30,925 | $3,644 | 120 | - | - | - | - | - | - | - | - |
$588 30,925 kWh |
$3,644 120 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.3511 USE PLANT OWNED TRANSFORMERS OR LEASE TRANSFORMERS |
Savings: $3,480 Cost: $1,500 |
- | - | - | - | $3,480 | - | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$3,480 - $ |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.2212 USE MINIMUM SAFE OVEN VENTILATION |
Savings: $3,222 Cost: $150 |
- | - | - | - | - | - | $3,222 | 348 | - | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$3,222 348 MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $2,840 Cost: $945 |
$670 | 35,320 | $2,170 | 71 | - | - | - | - | - | - | - | - |
$670 35,320 kWh |
$2,170 71 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.7314 REDUCE VENTILATION AIR |
Savings: $1,408 Cost: - |
- | - | - | - | - | - | $1,408 | 152 | - | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$1,408 152 MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.2514 COVER OPEN TANKS |
Savings: $315 Cost: - |
- | - | - | - | - | - | $296 | 32 | $19 | 2,244 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$296 32 MMBtu |
$19 2,244 Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
14: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $192 Cost: $600 |
$192 | 10,109 | - | - | - | - | - | - | - | - | - | - |
$192 10,109 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $127,589 Cost: $69,311 |
$19,328 | 1,019,346 | $61,260 | 2,003 | $3,480 | - | $41,698 | 4,503 | $939 | 110,719 | $884 | - | $19,328 1,019,346 kWh |
$61,260 2,003 kW-months/year |
$3,480 - $ |
$41,698 4,503 MMBtu |
$939 110,719 Tgal |
$884 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $17,921 Cost: $24,741 |
$2,325 | 122,405 | $9,123 | 299 | - | - | $6,473 | 699 | - | - | - | - | $2,325 122,405 kWh |
$9,123 299 kW-months/year |
- - $ |
$6,473 699 MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | Tgal | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Water Disposal | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Water Disposal | Ancillary Material Cost |